MI00472-3-EN
INSTALLATION MANUAL
4/4
ELECTRICAL CONNECTIONS
CAUTION
Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc...).
The device can only be powered by a power supply with a limited energy circuit 40Vdc / 28Vac max in output according
to CAN/CSA-C22.2 No.61010-1-12 / UL Std.No.61010-1 (3rd Edition) chapter 6.3.1/6.3.2 and 9.4 or class 2 according to
CSA 223/UL1310.
Use only copper or copper-coated aluminium or AL-CU or CU-AL conductors
These are open type devices intended for installation in a final casing/panel that offers mechanical protection and protection
against the spread of fire.
POWER SUPPLY
RS485 SERIAL PORT
RS232 SERIAL PORT
The power supply source must be protected from
any module malfunctions using appropriately-sized
safety fuses.
8
9
Vac / Vdc
Vac / Vdc
A (+)
B (-)
GND
1
2
3
3
4
5
6
7
GND
RTS
CTS
Rx
Tx
CAUTION
CAUTION
CAUTION
DIP - SWITCH SETTINGS
SW2 DIP-SWITCH:
Through DIP-SWITCH-SW2 it is possible to set the IP configuration of the device:
DESCRIPTION
DIP 1
DIP 2
To obtain the configuration from the Flash memory, both SW1
DIP switch selectors must be set to OFF
To reset the device to factory settings both SW1 DIP switches
must be set to ON
To force the device’s IP address to the standard value of
SENECA Ethernet products: 192.168.90.101
Reserved
The DIP-switch settings are read only at boot time. At each change, perform a restart.
SW1 DIP-SWITCH:
Through DIP-SWITCH-SW1 it is possible to set the polarization of the bus relative to the RS485 port:
DESCRIPTION
DIP 1
DIP 2
To polarize the bus on RS485, both SW1 DIP switch selectors
must be set to ON
NOT to polarize the bus on RS485, both SW1 DIP switch
selectors must be set to OFF
WARNING