![Seltron SGC26 Manual Download Page 33](http://html1.mh-extra.com/html/seltron/sgc26/sgc26_manual_1237168033.webp)
ENG
Service settings manual
33
Table with description of parameters :
Para-
meter
Function
Parameter description
Setting range Default
value
S3.1
SOLAR PUMP R2 OPERATI-
ON MODE
We define whether the pump R2 operates in ON/OFF mode or
in RPM mode.
RPM modulation of the pump is done with 5 stages: 40 %, 55
%, 70 %, 85 % and 100 %.
0- ON/OFF
1- RPM
1
S3.2
MIN. RPM FOR PUMP R2
Minimum RPM stage for modulation of pump R2.
1- 40 %
2- 55 %
3- 70 %
1
S3.3
R2 FULL-RPM RUNNING
TIME
When the differential condition is fulfilled, the R2 runs at full
RPM for a setted time.
5 ÷ 300 s
20
S3.8
SOLAR PUMP R3 OPERATI-
ON MODE
We define whether the pump R3 operates in ON/OFF mode or
in RPM mode.
RPM modulation of the pump is done with 5 stages: 40 %, 55
%, 70 %, 85 % and 100 %.
0- ON/OFF
1- RPM
1
Para-
meter
Function
Parameter description
Setting range Default
value
S2.13 MIN. COLLECTOR TEMPE-
RATURE
We define whether and how the minimum collector temperatu-
re is considered.
0- NO
1- YES
2- YES, ONLY
SWITCH-ON
2
S2.14 MIN. TEMP. OF AUX. HEAT
SOURCE Q1
We define whether and how the minimum temperature of
auxiliary heat source Q1 is considered.
0- NO
1- YES
2- YES, ONLY
SWITCH-ON
1
S2.15 MIN. TEMP. OF AUX. HEAT
SOURCE Q2
We define whether and how the minimum temperature of
auxiliary heat source Q2 is considered.
0- NO
1- YES
2- YES, ONLY
SWITCH-ON
1
S2.18 SENSOR T3 SUBSTITUTE
Selection of substitute sensor to replace the T3 sensor.
This setting is used when there is no option to install or con-
nect the sensor.
0- NO
1- SENSOR T1
2- SENSOR T2
0
S2.19 SENSOR T4 SUBSTITUTE
Selection of substitute sensor to replace the T4 sensor.
This setting is used when there is no option to install or con-
nect the sensor.
0- NO
1- SENSOR T1
2- SENSOR T2
3- SENSOR T3
0
S2.20 SENSOR T5 SUBSTITUTE
Selection of substitute sensor to replace the T5 sensor.
This setting is used when there is no option to install or con-
nect the sensor.
0- NO
1- SENSOR T1
2- SENSOR T2
3- SENSOR T3
4- SENSOR T4
0