SLC4075 TouchScreen Gateway Installation & Operating Manual
___________________________________________________________________________________________________
25
Description
Units
BACnet
Analog
Input
Present
Value
(Read
Only)
BACnet
Analog
Value
Present
Value
(Read
/Write)
Modbus
Analog
Input
Reg
Read
Only
Modbus
Holding
Reg
Read/
Write
Min
Val
Max
Val
TSGW
Page
PGW Relays, Set image
Binary
AV0054
400107
0
7
Rlys
PGW Relays, Invert Mask
Binary
AV0055
400109
0
7
Rlys
PGW Voltage Driver, Src Select
AV0056
400111
0
9
Voltage
Driver
PGW Voltage Driver Output
Pct
AV0057
400113
0
100
Voltage
Driver
XDI Logical Input
AI0018
300035
0
255
Expansion
Digital
Inputs
XDI Invert Mask
AV0008
400015
Expansion
Digital
Inputs
XDI Alarm Mask
AV0009
400017
Expansion
Digital
Inputs
XRLYS Set Relays
AV0010
400019
Expansion
Relays
XRLYS Src Select
AV0011
400021
Expansion
Relays
Table 5 Packed byte assignments
Convert the real value to an integer and decode
Parameter
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Remarks
GPA1/GPA2 Cfg
GPA2
Cfg
GPA1
Cfg
1=offset 4-20ma
0 No offset
GPDI
GPDI 4
GPDI 3
GPDI 2
GPDI 1
GPDI Invert Mask
GPDI 4
GPDI 3
GPDI 2
GPDI 1
Set bit to invert
sense
For Alarm monitoring by the BMS:
•
Determine which alarms are assigned to each of the General Purpose Digital Inputs
•
AI0038 is a packed byte with a weighted value for each bit position
•
Convert the real value to an integer and decode
GPDI Number
AI0038 Bit
Bit value
Example boiler assignment
GPDI 1
0
1
Low Water
GPDI 2
1
2
High Limit
GPDI 3
2
4
Low Flow
GPDI 4
3
8
Not used
Example AI0038 values:
•
AI0038 = 1 for a Low Water alarm
•
AI0038 = 4 for a Low Flow alarm
•
AI0038 = 1 + 4 =5 for a Low Water AND a Low Flow alarm
•
AI0038 = 2 + 4 = 6 for a High Limit AND a Low Flow alarm