www.selectronix.us
Selectronix, Inc.
(425) 788-2979
SLC4075 TouchScreen Gateway Installation & Operating Manual
___________________________________________________________________________________________________
22
Table 2 Building Management Interface –Most Commonly Used BACnet And Modbus
Addresses
Description
Units
BACnet
Analog
Input
Present
Value
Read
Only
BACnet
Analog
Value
Present
Value
Read/
Write
Modbus
Analog
Input
Reg
Read
Only
Modbus
Holding
Reg
Read/
Write
Min
Val
Max
Val
TSGW
Page
DDC, Aux/DDC Switch
AV0001
400001
0
90
All
DDC, Ld Lmt
Pct
AV0003
400005
0
99
TSGW
PGW PID1,Unmodified Set point
Deg F
AV0017
400033
-60
260
PID1
PGW RTD1 Temperature
Deg F
AI0031
300061
-60
260
RTD
Sensors
PGW SPM1, Modified Setpt
Deg F
AI0024
300047
-60
260
SPM1
PGW PID2, Unmodified Set pt
Pct
AV0033
400065
0
100
PID2
PGW RTD2 Temperature
Deg F
AI0033
300061
-60
260
RTD
Sensors
PGW SPM2, Modified Setpt
AI0025
300049
0
100
SPM2
S4K Percent Output, Master
Pct
AI0026
300051
0
100
SLC4000
S4K Percent Output, Exp01
Pct
AI0027
300053
0
100
SLC4000
S4K Percent Output, Exp02
Pct
AI0028
300055
0
100
SLC4000
S4K Percent Output, Exp03
Pct
AI0029
300057
0
100
SLC4000
PGW, GPA1
General Purpose Analog Input1
Span
Pct
AI0036
300071
-25
100
Aux
Sensors
PGW, GPA2
General Purpose Analog Input2
Span
Pct
AI0037
300073
-25
100
Aux
Sensors
PGW, GPDI *1
General Purpose Digital Inputs
Packed
byte
AI0038
300075
0
15
GPDI
PGW, GPA2 Value in Engr Units
Engr
Units
AI0040
300079
GPA2
PGW, PID P Term, in % Step Cmd
Pct
AI0041
300081
PGW, PID I Term, in % Step Cmd
Pct
AI0042
300083
PGW, PID D Term, in % Step Cnd
Pct
AI0043
300085