WM1700 ELECTRICAL SPECIFICATIONS 

INVERTER TYPE 

PWM Full Bridge power stage, with true sine wave AC output. 
 

SELECTRONIC WM1700 INVERTER SPECIFICATIONS 

ELECTRICAL

 

PARAMETER

 

WM1700

 

CONDITION

 

Output Power 
@ 25 °C Ambient 

1,700 watts 
2,250 watts 
4,500 watts 

Max Continuous 
1/2 Hour Rating 
Max Surge 

Output Power 
@ 40 °C Ambient 

1,500 watts 
2,000 watts 
4,500 watts 

Max Continuous 
1/2 Hour Rating 
Max Surge 

Voltage Input Range 

20 - 34V DC 

Range 

Input Current 

0.05A DC 

0.6A DC 

80A DC 

212A DC 

Stand By 
Inverter ON – No Load 
Max Continuous 25

°

Max Surge 25

°

Demand Start Sensitivity 
Response Time 
Factory Setting 

4-16W 

1 Second Max 

4W 

User Adjustable 
 
Factory Setting 

Low Voltage Shutdown 
High Voltage Shutdown 
Factory Setting  
(Low Voltage Shutdown) 

20 – 23.0V DC 

34V DC 

22.0V DC 

User Adjustable 
Fixed  
Factory Setting 

Output Voltage 

240V AC +/- 4% 

@ Nominal DC Input, 
No Load to Full Load 

Output Current 

7A AC 

18.75A AC 

Max Continuous 
Max Surge 

Output Wave Shape 
Output Frequency 
Total Harmonic Distortion 
Efficiency 

True Sine Wave 

50Hz +/- 0.01% 

< 4% 

Peak 94% Full Laod 90% 

Power Factor Limitations 

Nil 

Input / Output Isolation 

1,875VAC 

 

Memory Retention 

Permanent 

Operating Temperature Range  -10 °C to 50 °C 
Conforms to standards 

AS 3100 (wiring), AS 3108, C tick 

MECHANICAL 

 

Size 

410mm wide x 175mm high x 342mm deep 

 

 

Weight 

14kg 

Weight Packed 

17kg 

Input Lead Length 

1.5 metres 

Output Wiring Method 

Three terminal junction box with conduit knock outs 

Chassis 

Powder coated zinc steel (Wedgwood Blue) 

DC Isolation 

Single Pole Circuit Breaker ( Non auto) 

Warranty 

5 year parts and labour (Conditions apply) 

 

Notes:

  

The above specifications are based on unity power factor. 
The DC Input is electrically isolated from the AC Output.  
Through a policy of continued development, specifications are subject to change without notice 

 

Summary of Contents for WM1700-24V

Page 1: ...1700 24V OWNERS MANUAL Serial No _____________________________ Purchase Date ______________ Note Your warranty can only be valid once your warranty card is completed and returned to Selectronic Australia ...

Page 2: ......

Page 3: ...1 WM1700 MAINTENANCE 11 BATTERY MAINTENANCE 11 RADIO FREQUENCY INTERFERENCE 12 USING A SELECTRONIC KEYPAD WITH THE WM1700 24 13 SERIAL PORT WIRING 13 KEYPAD WIRING 13 KEYPAD FRONT PANEL Display not shown for clarity 13 STATUS 14 READINGS Keypad Grey Keys 14 SETTINGS Keypad Light Blue Keys 15 OPTIONS Keypad Light Blue Keys 16 DIAGNOSTICS Keypad Light Blue Keys 16 INVERTER ALARMS 16 WM1700 ELECTRICA...

Page 4: ...he Inverter must be installed in a dry cool dust free environment Please leave at least 300mm clearance around the sides and top of the Inverter and approximately 200mm at the base as this will aid the natural cooling of the Inverter The air vents on the underside of the WM1700 also need to be kept clear of obstructions BASE 300mm 300mm Mode PROUDLY DESIGNED MADE IN AUSTRALIA Demand Start Adjust L...

Page 5: ...inverter should be used If in any doubt see your supplier or installer BATTERIES High quality deep cycle batteries offer good performance and are available in a wide variety of sizes DO NOT USE ordinary car batteries or engine starting batteries If a battery is rated only in Cold Cranking Amps CCA and reserve capacity it is designed to start an engine Most hybrid type wet cell batteries will have ...

Page 6: ...aker on the front panel is in the OFF position LEVER DOWN Now connect the battery cables RED BATTERY POSITIVE BLACK BATTERY NEGATIVE These connections should be tight If using nuts bolts and washers they should be stainless steel At this point re check the connections before proceeding any further WARNING IF THE WM1700 EMITS A VERY LOUD TONE THE BATTERY LEADS HAVE BEEN CONNECTED IN REVERSE POLARIT...

Page 7: ...ng sound The WM1700 is now ready for use Mode Demand Start Adjust Low Volts Adjust Alarms 4 Watts DC Volts Low High TEMP Overload 8 Watts STATUS AC Volts ON AC Overload 12 Watts 16 Watts DEMAND START LED 1 LED 2 LED 3 LED 4 LED 5 Mode Button MODE BUTTON LED s The mode button allows adjustment of a number of user adjustable parameters within the WM1700 Five LED s are provided on the front panel to ...

Page 8: ... volts have risen sufficiently In this case charge the battery by starting the vehicle or using a battery charger The low voltage point that the inverter will cut out is adjustable to suit your particular battery LED 4 Temperature Overload should normally remain OFF If the inverter shuts down due to the heatsink getting too hot then this LED will come ON If the inverter shuts down due to the trans...

Page 9: ... button until the desired value is sought LED s 1 4 will return to Status Indication after 10 seconds if a key is not pressed Low Volts Cut out LED 1 LED 2 LED 3 LED 4 20 0 Volts ON 20 2 Volts Slow flash ON 20 4 Volts Medium flash ON 20 6 Volts Fast flash ON 20 8 Volts Fastest flash ON 21 0 Volts ON 21 2 Volts Slow flash ON 21 4 Volts Medium flash ON 21 6 Volts Fast flash ON 21 8 Volts Fastest fla...

Page 10: ...s could be potentially dangerous so we advise you to consult your system designer immediately 4 INVERTER SHUTS DOWN WITH LOW VOLTS If your WM1700 has shut down because of low DC volts it could be due to the following 1 A sustained large load could be causing the battery volts to drop below the cut out voltage a The Battery Bank is too small for the loads you wish to use consult your system designe...

Page 11: ...es of such high capacity it is essential that you wear protective clothing some form of eye protection and rubber soled work boots Please regard your batteries with a great deal of caution and if in any doubt entrust this work to your installer 1 Every week carry out a thorough visual inspection of all battery wiring taking particular note of the condition of inter connections between cells 2 Chec...

Page 12: ...I in your installation It is recommended that the power system including the inverter be housed at least 15 metres from the home Ensure an earth stake is placed as close to the inverter as possible and connected to the inverter via a short length of wire See the INSTALLATION section of this manual for wiring Avoid running DC cables into the home if at all possible If this cannot be avoided run DC ...

Page 13: ...Receive 7 White with brown stripe 8 Brown KEYPAD WIRING Serial Port looking at the base of the inverter 1 2 3 4 5 6 7 8 Keypad from rear 1 2 3 4 5 6 KEYPAD FRONT PANEL Display not shown for clarity NEXT DISPLAY UP DOWN SETTINGS OPTIONS DIAG NOSTICS CURRENT SHUNT 1 CURRENT SHUNT 2 CURRENT SHUNT 3 AC LOAD READINGS INPUT READINGS GENERATOR CONTROL INVERTER STATUS TIME BATTERY READINGS ALARM Remote Ke...

Page 14: ...t conserves valuable battery power when no appliances are on The amount of power or load that the Inverter needs to start up is adjustable see page 5 for details CONT mode CONTINUOUS means that the Inverter will be on at all times regardless of whether appliances are connected or not This situation is useful if you have small loads such as a VCR or digital clock that requires 24 hour power or if l...

Page 15: ...oggle between ON or OFF state This is set to ON at the factory Buzzer ON Set Parameters Indicates the end of the set parameters menu Press any grey keypad key to return you to the STATUS menu and save your settings Demand Start When in STANDBY mode the inverter will require a load of 4 watts or greater to turn on to full 240V power This setting can be adjusted between 4 to 16 watts In most cases t...

Page 16: ...ash and the buzzer will sound on an Inverter Alarm END Alarms Press the NEXT key to access diagnostics screens Press NEXT key Diagnostics Indicates transformer temperature Note the reading is NOT in degrees Celsius Tx Temp 1 Diagnostics Indicates Heatsink temperature Note the reading IS in degrees Celsius HS Temp 53C Diagnostics Indicates Demand Start current level D S I 2 Diagnostics Indicates th...

Page 17: ...Factory Setting Output Voltage 240V AC 4 Nominal DC Input No Load to Full Load Output Current 7A AC 18 75A AC Max Continuous Max Surge Output Wave Shape Output Frequency Total Harmonic Distortion Efficiency True Sine Wave 50Hz 0 01 4 Peak 94 Full Laod 90 Power Factor Limitations Nil Input Output Isolation 1 875VAC Memory Retention Permanent Operating Temperature Range 10 C to 50 C Conforms to stan...

Page 18: ...AL AS LANDLINE POWER It is necessary for your safety to ensure that all Remote Area Power System installations meet and comply with the relevant provisions and requirements of AS3000 wiring standards and AC wiring is installed by a Registered Electrical Contractor ...

Page 19: ...ncurred Unless otherwise specified to the purchaser the benefits conferred by this voluntary warranty are additional to all other conditions warranties guarantees rights and remedies expressed or implied by the Trade Practices Act in your state or territory All installation and user conditions as set down in the instruction manual must be strictly adhered to failure to do so may void your warranty...

Page 20: ...tral Nimbin NSW 2171 NSW 2480 Australia Australia Ph 02 9606 0279 Ph 02 6689 1430 Fax 02 6689 1109 Reid Technology Ltd 3 5 Auburn Street Solar Inverter Services Takapuna 13 Thirteenth Ave North Shore City Sawtell Auckland NZ NSW Ph 9 489 8100 2452 Fax 9 489 8585 Ph 02 66581733 ps reidtechnology co nz Suite 5 20 Fletcher Road Mooroolbark Victoria 3138 Australia Phone 61 3 9727 6600 Fax 61 3 9727 66...

Reviews: