background image

Function

Range or

Selection

Config. 

page

Factory

Setting

Password

1000

0000 to 9998

Change Password

New Password

No

1

1.1

No / Yes

0000 to 9998

1A, 5A to 

10,000A 

CT Primary

4

8

9

10

7

5

Network Selection

3P4W

2

3P4W, 3P3W, 1P2W-R, 

1P2W-Y and 1P2W-B

CT Secondary

1A or 5A  

3

5

350

5

100V to 500V

PT Secondary

PT primary

350

6

100V to 500kV

Reset energy 

Password

No

1001

0001 to 9999

Factory default

No

 Yes / No 

 Yes / No 

 Yes / No 

Reset active energy

No

NETWORK SELECTION AND WIRING INPUT 

Network selection in configuration mode

Wiring

3P4W

3P3W

3P4W, 2P3W

3P3W

Note : 

P1, P2 and P3 are Three Phase.

1P2W (P1/P2/P3)

1P2W (P1/P2/P3)

USER GUIDE

LED INDICATIONS

INT : 

The INT LED provides optical output for calibration

verification as well as visual indication of energy integration. 
The pulse rate is 1000 Pulses/kWh.

EXP :

 

EXP

 LED gives the indication of reversal of one or

more CT connections or presence of negative power in any 
or all phases. In such cases meter may not indicate the 
correct energy consumption. The CT should be connected to 
the meter with correct polarities.

NOTE :

 For resetting active energy, user will be prompted the password. If correct password is entered, the user 

will be able to reset all energy parameters. This password will be

 

a value which will be greater than the configuration 

password by 1.

Pulse output from meter can be interfaced into a process 
through a PLC for on line control of energy content in the 
process.
If the PLC has a self excited digital input, external DC 
supply is not needed. 
The kWh pulse is also used to derive average kWh 
information at the PLC.

 PROCESS INTEGRATION

APPLICATION OF PULSE OUTPUT

S2

S1

S2

S1

S2

S1

V1

N

V2

V3

I

1

I

2

I

3

EM306

L

N

24V DC

maximum

P
L
C

+

#

PULSE

OUTPUT

+

-

Pulse output from meter can be used as alarm generator 
or  total  energy  controller  by  interfacing  it  with  Pre
settable counter and control circuits (Contactors, Relay, 
Trip Circuit).

The  counter  is  loaded  with  the  maximum  energy 

consumption.  When  count  reaches  setpoint  it  provides 
output to control circuit to take appropriate action. 

 ENERGY CONTROLLER 

EM306 

S2

S1

S2

S1

S2

S1

V1

N

V2

V3

I

1

I

2

I

3

PULSE

OUTPUT

L

N

12 / 24V DC

+

#

To 

Control

Circuit 

C

O

U

N

T

E

R

+

I /

 P

O

 / 

P

All fuse types : 0.5A class CC UL type
                         0.5A fast acting 600V

#

+

-

APPLICATION OF PULSE OUTPUT

TYPICAL WIRING DIAGRAM 

3 PHASE 4-WIRE 

(COMMONLY USED) 

3 PHASE 4-WIRE 

(COMMONLY USED) 

3 Ø - 4 WIRE, 3 CT’S  

3 Ø - 4 WIRE, 3 CT’S  

LOAD

LOAD

LINE

LINE

L1

L1

L2

L2

L3

L3

N

N

#

#

S2

S2

S1

S1

S2

S2

S1

S1

S2

S2

S1

S1

N

N

V2

V2

V3

V3

I

1

I

1

I

2

I

2

I

3

I

3

V1

V1

EM306

L

L

L

L

N

N

N

N

PULSE

OUTPUT

PULSE

OUTPUT

+

+

--

3 PHASE 3-WIRE 

 3 Ø - 3 WIRE, 2 CT’S

S2

S1

S2

S1

S2

S1

N

V2

V3

I

1

I

2

I

3

V1

EM306

L

L

N

N

PULSE

OUTPUT

+

-

LOAD

LINE

#

L1

L2

L3

3 Ø - 4 WIRE, 3 CT’S and 3 PT’S

S2

S1

S2

S1

S2

S1

N

V2

V3

I

1

I

2

I

3

V1

EM306

L

L

N

N

PULSE

OUTPUT

+

-

LINE

LOAD

L1

L2

L3

N

#

 Doc. Name: OP INST EM306                        OP1029-V01(Page 2  of 3)

#

#

#