background image

Features :

EM306 :

!

  Single pulse output

!

  SMPS supply (85 to 276V)

!

  3Ø Active Energy meter

Energy Meter

EM306 / EM306-C-D

1

www.selec.com

  96 x 96mm

PRELIMINAR

Y

DAT

ASHEET

 

For EM306 :

  Transmission distance 

500 meter maximum

  Pulse output 

Voltage range : External 24V DC max

   

Current capacity : 100mA max

   

Pulse width : 100ms  ±5ms

  Baud rate 

9600  

  Transmission speed 

300, 600, 1200, 2400, 4800, 9600,  19200 (in bps)

  Communication interface                  RS485 and MODBUS RTU 

    Response time  

100ms (max and independent of baud rate)

  For EM306-C-D :

  Stop Bits  

1 or 2

Output specification

  Digits 

6

  LED indications  

Integration of energy (1000 Impulse / kWh)

  Display  

1 row, 7 segments LED Display

  Indications  

EXP - CT reverse indication

   

 

- Communication

   

DG  - Digital input

   

- Kilo

   

M  - Mega

Display specifications

  Active energy 

Class1

  Current nominal 

5A

 

Measurement accuracy

  VA Burden 

5A per phase

  Data update rate 

1 sec for all the parameters

 

Input-current

 

  CT ratings primary 

1 / 5A to 10kA (Programmable for any value)

  Electrical connection  

3Ø-3 wire, 3Ø-4 wire, 2Ø-3 wire, 1Ø-2 wire

 

Input-voltage

  PT primary 

100V to 500V AC (L - L) (Programmable for any value)

  Frequency range 

45 to 65Hz

Input specifications

  Voltage nominal 

11 to 300V AC (L – N), 19 to 519V AC (L – L)

  Supply voltage 

85 to 276V AC, 50/60 Hz

Auxiliary supply specifications

  Pollution degree 

Pollution degree II 

  Humidity (non - condensing)  

Up to 85% RH

  Altitude 

Up to 2000 meters

Environmental specifications

  Temperature  

Operating temperature : -10° to 55°C

   

Storage temperature : -20° to 75°C  

  Wire gauge at terminals 

20 to 14AWG;75°C

  Type of keys 

Touch

  No. of keys 

4

  Weight  

210gms

Mechanical specifications

  Mounting  

Panel

  Torque at terminals 

0.68N-m to 0.79 N-m 

PULSE 

OUTPUT

Dimensions (All are in mm)

Terminal connection

EM306

Display specifications

  Display 

1 row, 7 segments LED Display

  Digits 

6

   

For Power : Auto resolution,

   

For Power factor : 0.001 (for EM306-C-D)

  Digit height 

0.56"

  Resolution 

For energy : 0.01k, 0.1k, 1k, 0.01M, 0.1M, 1M,10M

   

(depending upon CT ratio x PT ratio)

  VA burden 

0.5VA per phase

  Impedance 

≥0.8MOhm

  Frequency 

±0.1% For L - N Voltage >20V,

   

For L - L Voltage >35V*

  Frequency range 

45 - 65Hz

  Power 

1%*

  Reactive energy 

Class 2*

 

Input-current

  Current nominal 

5A

  VA burden 

0.5VA per phase

  CT ratings primary 

1 / 5A to 10kA (Programmable for any value)

  Active energy  

Class 1 

 

Measurement accuracy

 

  Frequency range 

45 - 65Hz

  Power factor 

±0.01 Digit*

  Withstand continuous 

120A for 1sec

  Type of measurement 

TRUE RMS 

  Electrical connections 

3Ø - 3 wire, 3Ø - 4 wire, 2Ø - 3 wire, 1Ø - 2 wire

  Sampling rate 

100 Samples / Cycle

  Data update rate 

1 sec for all the parameters*

 

Input-voltage

  PT primary 

100V to 500V AC (L - L)

   

(Programmable for any value)

  Voltage nominal 

11 to 300V AC (L – N), 19 to 519V AC (L – L)

Input specifications

 

Weight 

210gms

  IP degree of protection 

IP54

  Material 

MAKROLON 6557 SMOKE BLACK

Mechanical specifications

  Wire gauge at terminals 

20 to 14AWG;75°C

  Torque at terminals 

0.68N-m to 0.79 N-m

  Mounting position 

Panel mount

Auxiliary supply specifications

 

Supply voltage 

85 to 276V AC, 50/60 Hz

  Humidity 

85% (Non-Condensing)

Environmental specifications

 

Operating temperature 

-10°C to +55°C 

  Altitude 

Up to 2000 meters 

  Measurement category 

CAT III

  Storage temperature 

-20°C to 75°C  

  Pollution degree 

2

Dimensions (All are in mm)

99

99

91.5

91.5

90.5

5

50

Side view

Front bezel

Panel cutout

NOTE - 

 

=

 

Only for EM306-C-D

*

  Pulse output 

Voltage range : External 24V DC max

   

Current capacity : 100mA max

   

Pulse width : 100ms  ±5ms

 

For EM306 :

Output specification

  Transmission speed 

300, 600, 1200, 2400, 4800, 9600, 19200 

  Transmission distance 

500 meter maximum 

  Response time 

100ms (max and independent of baud rate)

  Stop bits 

1 or 2

  Isolation 

Yes

  Transmission mode 

Half duplex

 

For EM306-C-D :

Output specification

  Device ID & Parity 

1 to 255 & None, Odd, Even 

  Protocol & Interface 

RS485 and MODBUS RTU

  Baud rate 

9600

EM306-C-D :

!

  Dual Input Meter (Mains / D.G.)

!

  RS485 Communication MODBUS RTU Protocol

!

  3Ø Energy (kWh, kVArh, kVAh)

!

  3Ø Power (kW, kVAr, kVA), PF

Reviews: