SEL-3061 Data Sheet

Schweitzer Engineering Laboratories, Inc.

8

                    

For more information on the SEL-3061 accessories and 
antenna installation, refer to the 

SEL-3061 Instruction 

Manual

 or the 

SEL Radio Accessories Guide

.

Diagrams and Dimensions

                    

                    

Table 3  Signal Loss at 2155 MHz

Cable Type

Characteristic 
Impedance

3.05 m 
(10 ft)

12.24 m 
(50 ft)

30.48 m 
(100 ft)

RG-8X 
(SEL-C980 or 
SEL-C964)

50 

2.0 dB

10.1 dB

Do Not 
Use

LMR-400 
(SEL-C966 or 
SEL-C968)

50 

0.6 dB

3.1 dB

6.2 dB

7/8" HELIAX 
(SEL-C978)

50 

Do Not 
Use

0.97 dB

1.94 dB

                    

Figure 7  SEL-3061 Front-Panel Diagram

                    

Figure 8  SEL-3061 Rear-Panel Diagram

Summary of Contents for SEL-3061

Page 1: ...evels for configuration maintenance and usage Supports Remote Authentication Dial In User Service RADIUS Syslog Logs system events for alerts in a consistent fashion for both local and centralized collection Network Management Supports SNMP reads and traps for versions v1 v2c and v3 Application Versatility Serial and Ethernet ports enable communications with a variety of end devices Dual Mode Oper...

Page 2: ... settings changes and firmware upgrades Ubiquitous Connectivity The SEL 3061 supports 4G LTE and 3G cellular technol ogy and uses cellular networks to provide wireless con nectivity for a variety of critical infrastructure devices Reporting and Alarms The SEL 3061 uses the Syslog format to log events The router maintains an internal record of as many as 30 000 event logs in nonvolatile memory that...

Page 3: ...ith secure tunneling provides application flexibility and makes installation easy with out sacrificing security SCADA The SEL 3061 provides the communications link to aggregate data from field devices and forwards it to SCADA systems and HMIs The SEL 3061 can be used in data acquisition and slow to medium speed control applications SCADA includes analog and discrete I O monitoring and metering The...

Page 4: ...puts In some instances it is necessary to perform data acquisition on the status or value of the connected I O A distributed data acquisition system uses an automation controller as the data concentrator and a computer as the SCADA host The system uses remote discrete and analog I Os As shown in Figure 3 a single SEL 3061 at each site both provides the connectivity between these remote I Os with t...

Page 5: ...ovides wide area load monitoring and fault location from line powered SEL FLT devices The SEL FLR collects load data and fault information from the SEL FLT devices and sends the collected data to an Operation Management System OMS or Energy Management System EMS via a WAN The SEL 3061 provides the communications link between the OMS and the SEL FLR When connected to the SEL FLR the SEL 3061 provid...

Page 6: ...061 by using either the serial or Ethernet interface Capacitor Bank Controls The SEL 3061 provides communication for remote mon itoring and automated or manual control of capacitor banks Pump Automation Controls Monitor and control critical infrastructure such as water and wastewater pumps by using the SEL 3061 to pro vide remote access to SEL 2411P Pump Automation Controllers During both routine ...

Page 7: ...ollowing accessories are available for use with the SEL 3061 Figure 6 SEL 3061 HTTPS Device Webpage Table 1 Available Antennas Part Number Description 235 0003 Low profile 3 dBi Omnidirectional 698 960 MHz 1710 2700 MHz N Female Connector 235 0242 Indoor Right Angle Antenna 698 960 MHz 1710 2700 MHz SMA Male Connector Table 2 Optional Antenna Mounting Hardware Part Number Description 915900497 Mou...

Page 8: ...adio Accessories Guide Diagrams and Dimensions Table 3 Signal Loss at 2155 MHz Cable Type Characteristic Impedance 3 05 m 10 ft 12 24 m 50 ft 30 48 m 100 ft RG 8X SEL C980 or SEL C964 50 2 0 dB 10 1 dB Do Not Use LMR 400 SEL C966 or SEL C968 50 0 6 dB 3 1 dB 6 2 dB 7 8 HELIAX SEL C978 50 Do Not Use 0 97 dB 1 94 dB Figure 7 SEL 3061 Front Panel Diagram Figure 8 SEL 3061 Rear Panel Diagram ...

Page 9: ...Schweitzer Engineering Laboratories Inc SEL 3061 Data Sheet 9 Figure 9 SEL 3061 Dimensions for Rack and Panel Mount Models 6 59 167 4 3 00 76 2 4 93 125 2 1 69 42 9 7 07 179 6 06 1 5 ...

Page 10: ...yslog Transmission Control Protocol TCP Transport Layer Security TLS User Datagram Protocol UDP Security User Based Accounts Password Length 8 4096 characters Password Set A Z a z 0 9 special characters User Roles Administrator Engineer Monitor Syslog Storage for 30 000 local Syslog messages SNMP Monitors diagnostics through SNMP v1 v2c and v3 read operations Sends notifications by using SNMP v1 v...

Page 11: ...Power Port IEC 61000 4 29 2000 Surge Withstand IEC 61000 4 18 2005 A1 2010 Capability Immunity 2 5 kV common mode 1 kV differential mode Conducted RF Immunity IEC 61000 4 6 2013 10 Vrms Surge Immunity IEC 61000 4 5 2005 Zone B 0 5 1 0 kV line to line Zone B 0 5 1 0 2 0 kV line to earth EMC Emissions Radiated Emissions CISPR 11 2009 A1 2010 CISPR 22 2008 ANSI C63 4 2015 47 CFR Part 15 107 109 ICES ...

Page 12: ...ment is provided for informational use only and is subject to change without notice Schweitzer Engineering Laboratories Inc has approved only the English language document This product is covered by the standard SEL 10 year warranty For warranty details visit selinc com or contact your customer service representative PDS3061 01 2350 NE Hopkins Court Pullman WA 99163 5603 U S A Tel 1 509 332 1890 F...