Schweitzer Engineering Laboratories, Inc.

SEL-2241 Data Sheet

3

Outputs

Refer to 

Specifications on page 5 

for output contact rat-

ings and 

Figure 2

 for terminal assignments. Configure

the contact output under SystemTags (Contact Outputs
Tab) in 

AC

SEL

ERATOR

 RTAC. You can change the name

of the point, create an alias tag name, and initialize status
values. The RTAC will use the initialized value until run
time, when it uses the actual value.

Figure 4

 shows that a trip coil has a resistive and induc-

tive component. After a trip output has been closed for a
long time, the current settles to a steady-state value.
When the trip output opens, it tries to interrupt the induc-
tive current that wants to continue to flow (V = L di/dt).
This attempted interruption of current causes a large
voltage spike that can turn into an arc. When the contacts
bounce during the arc, they often weld closed. SEL has
designed, tested, and specified the outputs for this appli-
cation to prevent any such welding. See the 

Breaking

Capacity on page 6

.

Figure 4

Inductive Interrupt of a Trip Output

LED Indicators

In addition to LEDs representing module status and com-
munications activity, the SEL-2241 has three user-pro-
grammable bi-color LEDs. Configure these LEDs under
SystemTags (LEDs Tab) in 

AC

SEL

ERATOR

 RTAC.

Field Serviceability

You can upgrade RTAC firmware and custom program-
ming in the field or remotely over Ethernet. Self-tests
provide status indication of errant conditions that can
occur in the RTAC. You can map one or a combination of
these or other status indications to the alarm contact to
create a diagnostic alarm.

Module Replacement

To replace the SEL-2241 RTAC, perform the following
steps.

Step 1. Back up all RTAC settings. See 

Section 1: 

Getting Started 

in the

 SEL-5033 Instruction 

Manual

 for instructions on how to back up and 

restore RTAC projects.

Step 2. De-energize any power source connected to the 

power coupler(s) in the Axion node.

Step 3. Loosen retaining screws and remove the 

terminal strip for the alarm contact. Disconnect 
all communications cables.

Step 4. Loosen the chassis retaining screw at the top of 

the module.

Step 5. Tip the top of the module away from the chassis 

and lift it from the bottom lip.

Step 6. Install the new module according to the 

applicable mechanical installation instructions 
in this section.

Step 7. Make all necessary connections to the module 

according to the applicable connection 
instructions in this section.

Step 8. Apply power to the Axion node.

Step 9. Use IP address 172.29.131.1 to access the RTAC 

web interface through the supplied USB cable. 
See 

Section 7: Security and Account 

Management 

in the

 SEL-5033 Instruction 

Manual

 for RTAC web password setup. Also 

enable all necessary communications ports.

Step 10. Download the settings project from 

AC

SEL

ERATOR

 RTAC.

Real-Time Clock Battery Replacement

The only field-replaceable component is the real-time
clock battery, which cannot be recharged. A lithium bat-
tery powers the clock (date and time) during loss or
removal of the external power source. The battery is a
3 V lithium coin cell, Rayovac no. BR1632 or equiva-
lent. At room temperature (25°C), the battery will oper-
ate nominally for ten years. When the device receives
power from an external source, the battery experiences a
low self-discharge rate. Thus, battery life can extend well
beyond ten years.

To replace the real-time clock battery, perform the fol-
lowing steps.

Step 1. Follow the 

SEL-2241 Disassembly

 instructions 

to expose the circuit board.

Step 2. Locate the battery clip (holder) on the board.

Step 3. Carefully remove the battery from beneath the 

clip. Properly dispose of the old battery.

125 Vdc 

Summary of Contents for SEL-2241

Page 1: ...2242 chassis backplane has ten slots labeled A through J Only Slot A supports the SEL 2241 RTAC module To install the RTAC tip the top of the module away from the chassis align the notch on the bottom...

Page 2: ...eb interface through the USB cable See Section 7 Security and Account Management in the ACSELERATOR RTAC SEL 5033 Instruction Manual for RTAC web password setup The SEL 2241 has four nonisolated seria...

Page 3: ...ection 1 Getting Started in the SEL 5033 Instruction Manual for instructions on how to back up and restore RTAC projects Step 2 De energize any power source connected to the power coupler s in the Axi...

Page 4: ...ection 3 Factory Reset in the SEL 2240 Instruction Manual describes Table 3 shows the configurable jumper positions SEL 2241 Disassembly To disassemble the SEL 2241 RTAC perform the fol lowing steps S...

Page 5: ...EtherNet IP Explicit Message Client Server DNP3 Serial DNP3 LAN WAN Modbus RTU Modbus TCP SEL Fast Messaging LG 8979 SES 92 IEEE C37 118 IEC 61850 MMS IEC 60870 5 101 104 FTP SFTP CDC Type II EtherNe...