background image

Schweitzer Engineering Laboratories, Inc.

SEL-2241 Data Sheet

5

Specifications

Compliance

Designed and manufactured under an ISO 9001 certified quality 

management system

UL Listed to U.S. and Canadian safety standards (File E220228; 

NRAQ, NRAQ7)

CE Mark

General

Operating Temperature Range

–40° to +85°C (–40° to +185°F)

Note: 

Not applicable to UL applications.

Operating Environment

Pollution Degree:

2

Overvoltage Category:

II

Insulation Class:

1

Relative Humidity:

5%–95%, noncondensing

Maximum Altitude:

2000 m

Dimensions

Refer to 

Section 2: Installation

 in the 

SEL-2240 Instruction Manual

 for 

relay dimensions.

Weight (Fully Populated Node)

7.26 kg (16 lb

CPU

Processing and Memory

Processor Speed:

533 MHz

Memory:

1024 MB DDR2 ECC RAM

Storage:

4 GB (2 GB reserved)

Security Features

Account Management:

User Accounts

User Roles
LDAP Central Authentication
RADIUS Central Authentication
Strong Passwords
Inactive Account Logouts

Intrusion Detection:

Access/Audit Logs
Alarm LED
Alarm Contact

Encrypted 

Communication:

SSL/TLS, SSH, HTTPS

Automation Features

Protocols

Client:

DNP3 Serial, DNP3 LAN/WAN, Modbus 

RTU, Modbus TCP, SEL ASCII, SEL 
Fast Messaging, LG 8979, IEEE C37.118, 
IEC 61850 MMS, CP2179, IEC 60870-5-
101/104, SNMP, CDC Type II, Courier, 
IEC 60870-5-103, EtherNet/IP Explicit 
Message Client

Server:

DNP3 Serial, DNP3 LAN/WAN, Modbus 

RTU, Modbus TCP, SEL Fast Messaging, 
LG 8979, SES-92, IEEE C37.118, 
IEC 61850 MMS, IEC 60870-5-101/104, 
FTP, SFTP, CDC Type II, EtherNet/IP 
Implicit Message Adapter

Peer-to-Peer: SEL 

M

IRRORED

 B

ITS

 Communications, 

IEC 61850 GOOSE, Network Global 
Variables (NGVL)

Fieldbus:

EtherCAT Client (in RTAC), EtherCAT 

Server (I/O modules)

Engineering Access

Modes:

SEL Interleaved, Direct

Port Server:

Map Serial Ports to IP Ports

Secure Web Server:

Diagnostic and Communications Data

Time-Code Input (Modulated IRIG-B)

Input Impedance:

2 k

Accuracy:

500 µs

Time-Code Input (Demodulated IRIG-B)

On (1) State:

V

ih

 > 2.2 V

Off (0) State:

V

il

 < 0.8 V

Input Impedance:

2 k

Accuracy:

500 ns

Time-Code Output (IRIG-B)

On (1) State:

V

oh

 > 2.4 V

Off (0) State:

V

ol

 < 0.8 V

Load:

50 

Network Time Protocol (NTP) Modes

NTP Client:

As many as three configurable servers

NTP Server

Precise Time Protocol (PTP)

PTP Client:

Peer delay request and end-to-end path 

delay supported

Communications Ports

Ethernet Ports (To Backplane)

Ports:

1

Data Rate:

Automatic

Protocols:

Dedicated EtherCAT port

Ethernet Ports (Terminal Side)

Ports:

2

Data Rate:

10 or 100 Mbps

Connector:

RJ45 Female or LC Fiber Single-Mode or 

Multimode (100 Mbps only)

Fiber-Optic Ports (Class 1 LASER/LED)

Wavelength:

1300 nm

Optical Connector Type:

LC

Multimode Option

Link Budget:

11 dB

Min. TX Power:

–20 dBm

Min. RX Sensitivity:

–31 dBm

Fiber Size:

50–200 µm

Approximate Range:

2 km

Summary of Contents for SEL-2241

Page 1: ...2242 chassis backplane has ten slots labeled A through J Only Slot A supports the SEL 2241 RTAC module To install the RTAC tip the top of the module away from the chassis align the notch on the bottom...

Page 2: ...eb interface through the USB cable See Section 7 Security and Account Management in the ACSELERATOR RTAC SEL 5033 Instruction Manual for RTAC web password setup The SEL 2241 has four nonisolated seria...

Page 3: ...ection 1 Getting Started in the SEL 5033 Instruction Manual for instructions on how to back up and restore RTAC projects Step 2 De energize any power source connected to the power coupler s in the Axi...

Page 4: ...ection 3 Factory Reset in the SEL 2240 Instruction Manual describes Table 3 shows the configurable jumper positions SEL 2241 Disassembly To disassemble the SEL 2241 RTAC perform the fol lowing steps S...

Page 5: ...EtherNet IP Explicit Message Client Server DNP3 Serial DNP3 LAN WAN Modbus RTU Modbus TCP SEL Fast Messaging LG 8979 SES 92 IEEE C37 118 IEC 61850 MMS IEC 60870 5 101 104 FTP SFTP CDC Type II EtherNe...

Page 6: ...Ithe Rating 5 A Rated Frequency 50 60 5 Hz Operating Time coil energization to contact closure resistive load Pickup Dropout time 8 ms typical Electrical Durability Make VA Rating 3600 VA cos 0 3 Elec...

Page 7: ...Power Supply Immunity IEC 61000 4 11 2004 IEC 61000 4 29 2000 IEC 60255 11 2008 Magnetic Field Immunity IEC 61000 4 8 2009 Severity Level 1000 A m for 3 seconds 100 A m for 1 minute IEC 61000 4 10 200...

Page 8: ...oducts including without lim itation software firmware and documentation The information in this document is provided for informational use only and is subject to change without notice Schweitzer Engi...