Sel 3355-2 Manual Download Page 10

SEL-3355-2 Data Sheet

Schweitzer Engineering Laboratories, Inc.

10

Electromagnetic Compatibility Immunity

Conducted RF:

IEC 61000-4-6:2013

Severity Level: 10 Vrms

Electrostatic Discharge:

IEC 61000-4-2:2008
IEEE C37.90.3-2001

Severity Level:

2, 4, 6, 8 kV contact discharge;
2, 4, 8, 15 kV air discharge

Fast Transient/Burst:

IEC 61000-4-4:2012

Severity Level: Class A

4 kV, 5 kHz on power supply and outputs;
2 kV, 5 kHz on communications lines

Magnetic Field:

IEC 61000-4-8:2009

Severity Level:

1000 A/m for 3 s
100 A/m for 1 m

Power Supply:

IEC 61000-4-11:2004
IEC 61000-4-17:1999+A1:2001+A2:2008
IEC 61000-4-29:2000

Radiated Radio Frequency: IEC 61000-4-3:2006+A1:2007

Severity Level: 10 V/m

IEEE C37.90.2-2004

Severity Level: 20 V/m

Surge Withstand 

Capability:

IEC 61000-4-18:2006+A1:2010

Severity Level:

Power supply and outputs

2.5 kV peak common mode
1.0 kV peak differential mode

Communications ports

1.0 kV peak common mode

IEEE C37.90.1-2012

Severity Level:

2.5 kV oscillatory
4 kV fast transient

Surge Immunity:

IEC 61000-4-5:2005

1 kV line-to-line
2 kV line-to-earth
2 kV communications ports

Environmental

Change of Temperature:

IEC 60068-2-14:2009

Severity Level:

5 cycles, 1°C per minute ramp
–40° to +60°C (E3-1505M CPU)
–40° to +75°C (E3-1505L CPU)

Cold, Operational:

IEC 60068-2-1:2007 

Severity Level: 16 hours at –40°C

Cold, Storage:

IEC 60068-2-1:2007

Severity Level: 16 hours at –40°C

Damp Heat, Cyclic:

IEC 60068-2-30:2005 

Severity Level:

12 + 12-hour cycle
25° to 55°C, 6 cycles, >93% relative 

humidity

Damp Heat, Steady:

IEC 60068-2-78:2012

Severity Level:

40°C, 240 hours, >93% relative 

humidity

Dry Heat, Operational:

IEC 60255-1:2009
IEC 61850-3:2013
IEC 60068-2-2:2007

Severity Level:

16 hours at 60°C (E3-1505M CPU)
16 hours at 75°C (E3-1505L CPU)

Dry Heat, Storage:

IEC 60255-1:2009
IEC 61850-3:2013
IEC 60068-2-2:2007

Severity Level: 16 hours at 85°C

Free Fall:

IEEE 1613-2009

Severity Level: 100 mm

Vibration:

IEC 60255-21-1:1988

Severity Level:

Endurance Class 2
Response Class 2

IEC 60255-21-2:1988

Severity Level:

Shock Withstand, Bump Class 1
Shock Response Class 2

IEC 60255-21-3:1993

Severity Level:

Quake Response Class 2

Safety

Enclosure Protection:

IEC 60529:2001 + CRGD:2003

Severity Level: IP30

Dielectric Strength:

IEC 60255-27:2013
IEEE C37.90-2005

Severity Level:

3600 Vdc on power supply
2500 Vac on contact output
1500 Vac Ethernet ports
Type tested for one minute

Impulse:

IEC 60255-27:2013
IEEE C37.90-2005

Severity Level:

5 kV common mode, power supply, 

contact outputs

1.5 kV Ethernet ports

Summary of Contents for 3355-2

Page 1: ...he need for external inverters and enhance system reliability availability and serviceability You can install software from SEL and third party software ven dors to customize the SEL 3355 2 for your s...

Page 2: ...The SEL 3355 2 supports as many as four standard PCIe form factor expansion cards and one 32 bit PCI card enabling you to customize the system I O to meet your application needs Choose from a selectio...

Page 3: ...ea net works LANs for control data or engineering access Time The SEL 3390S8 serial expansion card accepts IRIG B time code input for precise time input and distribution to connected devices EIA 232 E...

Page 4: ...re 4 SEL 3355 2 as Remote Read Only Domain Controller Performing Central Authentication Using LDAP Disturbance Recording System for PRC 002 2 Figure 5 Reliable Hardware for Running Your Disturbance Re...

Page 5: ...Ds for your custom application i USB Ports Two easily accessible ports to connect USB 3 1 peripherals o SATA Drive Bay Removable cover plate enables easy access to SATA drives from the front panel i y...

Page 6: ...SEL 3355 2 Data Sheet Schweitzer Engineering Laboratories Inc 6 Product Dimensions Figure 9 SEL 3355 2 Dimensions for Rack and Panel Mount Models...

Page 7: ...Hz base 2 8 GHz turbo Cache 1 MB L2 8 MB L3 Intel Xeon E3 1505M Quad Core Speed 2 8 GHz base 3 7 GHz turbo Cache 1 MB L2 8 MB L3 RAM 4 64 GB DDR4 ECC PC4 17000 2133 MHz Chipset Intel CM236 Chipset Exp...

Page 8: ...SEL 3390S8 Expansion Cards As many as 24 additional EIA 232 422 485 ports RJ45 connectors 300 to 921600 bps Note See the SEL 3390S8 instruction manual for additional information Meets EIA TIA 562 Spec...

Page 9: ...min Size 12 18 AWG Tightening Torque Minimum 0 6 Nm 5 in lb Maximum 0 8 Nm 7 in lb Crimp Ferrule Recommended Mounting Ear Tightening Torque Minimum 0 18 Nm 1 6 in lb Maximum 0 25 Nm 2 2 in lb Groundi...

Page 10: ...14 2009 Severity Level 5 cycles 1 C per minute ramp 40 to 60 C E3 1505M CPU 40 to 75 C E3 1505L CPU Cold Operational IEC 60068 2 1 2007 Severity Level 16 hours at 40 C Cold Storage IEC 60068 2 1 2007...

Page 11: ...pset Heaterb cold startup 5 C 41 F continuous operation 0 C 32 F continuous operation 40 C 40 F N A 0 W 0 W N A 5 W 20 W 90 W 10 W 40 W a Minimum 0 load on all components minimum power consumption sta...

Page 12: ...d international copyright and patent laws in its products including without lim itation software firmware and documentation The information in this document is provided for informational use only and...