4.2 Checklist prior to start-up
þ
1.
Verify that the weighing unit/units are correctly installed. See the instructions for the weighing unit.
þ
2.
Verify that the correct wiring and cable connections have been made. Refer to section 3 in this
manual.
þ
3.
Verify that the belt revolution sensor is installed. The belt must have a sensor that senses a fixed
position of the belt once/belt revolution. If no sensor is installed, functions will be the same as for
model H14.
þ
4.
Verify that the tachometer is installed correctly. Refer to the manual for the tachometer and weighing
unit. If the tachometer is installed with drive type CF,(where the tacho is driven by a heavy wheel,resting
against the belt) you can skip to check no.5 below.
þ
4.1
If the tachometer is being driven in any other way, measure the total belt length in cm and move
to step no.5
þ
5.
The parameter values below will be necessary for the start-up procedure. Make notes of the following
values, so that you have them at hand when performing the start-up procedure.
!
Type of load cell
installed in the weighing unit;
Rated load in kg
and
output in mV/V
.
!
Idler distance
at the weighing area. To be measured precisely to +/- 1mm. Refer to the instruction
manual for the weighing unit for detailed information.
!
Belt length
, (only necessary if drive unit CF is
not
installed).
18-08-16
S44-H15E
4-2
S-E-G
SYSTEM A2-H15 INSTRUCTION