background image

28  

TD_MRI1_06.05_GB 

6.4.7  

Example of a test circuit for 

MRI1

 

 

relay with directional feature 

 

 

 

Figure 6.2: 

Test circuit 

For testing relays with directional feature, current and 
voltage input signals with adjustable phase shifting are 
required. Figure 6.2 shows an example of a single 
phase test circuit with adjustable voltage and current 
energizing the 

MRI1

 relay under test. 

For testing a relay with directional feature, one of the 
input energizing quantity (voltage) shall be applied to 
the relay with a constant value within its effective 
range. The other input energizing quantity (current) 
and phase angle shall be appropriately varied. 

MRI1

 is a three phase directional time overcurrent re-

lay with relay connection angle of 0°. The relay input 
currents and their corresponding reference voltages are 
shown in the following table (refer to 4.3): 
 
If the single phase test circuit as illustrated in  
Figure 6.2 is applied to test the directional feature of 
the relay and the current source is connected to  
phase 1 current input (B3/B4), then the voltage source 
should be connected to relay terminals A5/A7. 

 
 
 
In order to test the directional feature, all activation 
points should first be set to “EXIT”. Then a test voltage 
equivalent to the rated voltage is connected to termi-
nals A5/A7 and a current of 1 x In is impressed upon 
the current inputs B3/B4. 
It is now possible to read and check all measured val-
ues in accordance with Table 6.1. If the phase posi-
tion is changed, the values I

Q

 and I

P

 change. If the an-

gle is changed by 90

o

, for example, the measured va-

lue for current input I1 must be 1.0 for I

P

 and +/- 0.0 

for I

Q

 

Determining the change in direction 

    
The angle of greatest sensitivity for determining the 
phase direction is adjustable between 15

o

 and 83

o

Consequently, the greatest sensitivity is achieved with 
setting 49

o

 if the input current leads the input voltage 

by 49

o

. This setting results in a tripping range in ad-

vance direction of 139

o

 leading to 41

o

 lagging if the 

marginal regions are neglected on account of lack in 
measuring precision. 

Summary of Contents for HighTECH Line

Page 1: ...CTION TECHNOLOGY MADE SIMPLE DIGITAL MULTIFUNCTIONAL RELAY FOR TIME OVERCURRENT PROTECTION HighTECH Line DIGITAL MULTIFUNCTIONAL RELAY FOR TIME OVERCURRENT PROTECTION Revision A Original document Engl...

Page 2: ...for earth fault element tIE 5 2 14 Reset mode for inverse time tripping in earth current path 5 2 15 Current setting for high set element of earth fault supervision IE 5 2 16 Trip delay for high set...

Page 3: ...h fault protection E X Type 7 3 4 Earth fault protection ER XR Type 7 3 5 Switch failure protection 7 3 6 Interface parameter 7 3 7 Inverse time overcurrent protection relay 7 3 8 Direction unit for p...

Page 4: ...e measured values by using dis crete Fourier analysis to suppress the high frequence harmonics and DC components induced by faults or system operations Selectable protective functions between definite...

Page 5: ...the connection has to be realized as per Figure 3 1 and Figure 3 2 Figure 3 3 Phase current measuring and earth current detection by means of Holmgreen circuit This connection can be used with three...

Page 6: ...inally fed to the analog digital converter For the unit type with earth fault directional features ER XR relay type the residual voltage UE in the sec ondary circuit of the voltage transformers is int...

Page 7: ...t MRI1 To prevent that the C B trip coil circuit is interrupted by the MRI1 first i e before interruption by the C B auxiliary contact a dwell time is fixed This setting ensures that the MRI1 remains...

Page 8: ...X soli resi X X X tCBFP X X X X X X X X X X X 50 60 Hz X X X X X X X X X X X LED Flash X X X X X X X X X X X RS485 Slaveaddress X X X X X X X X X X X Baud Rate 3 X X X X X X X X X X X Parity Check 3...

Page 9: ...RESET ENTER TRIP t I I E CHAR I t E I I E tI E EARTH E RS E DISPLAY Figure 3 8 Front panel MRI1 E X SELECT RESET ENTER TRIP t I I CHAR I tI I tI PHASE MRI1 IR L1 L2 L3 RS Q I P I DISPLAY Figure 3 9 F...

Page 10: ...display At pickup trip and parameter setting the green LED lights up to indi cate the forward direction the red LED indicates the reverse direction The LED marked with letters RS lights up during sett...

Page 11: ...induced transients or other system dis turbances The calculated actual current values are compared with the relay settings If a phase current exceeds the pickup value an alarm is given and after the s...

Page 12: ...s at least 2 periods 40 ms at 50 Hz are evaluated For the MRI1 overcurrent relays with directional feature different time delays or time multipliers can be set for forward and backward faults ref to c...

Page 13: ...ing the relay Earth faults beyond the current transformers i e on the consumer or line side will not be detected Figure 4 4 Generator stator earth fault protetion 4 4 2 System earth fault protection W...

Page 14: ...n be measured in three different ways depending on the voltage transformer connec tions refer to Table 4 1 Total current can be measured by connecting the unit either to a ring core C T or to cur rent...

Page 15: ...e current for faulted and non faulted lines in case of compensated systems cos UE residual voltage IE zero sequence current IL inductive component of zero sequence current caused by Petersen coil IC c...

Page 16: ...earthed system are pre dominantly ohmic in character with a small inductive part The characteristic angle for these types of system has therefore been set at 170 in relation to the zero sequence volta...

Page 17: ...E changeover of isolated sin or compensated cos networks for ER XR type SIN COS SELECT RESET Change over of solidly resistance earthed networks SR type SOLI RESI SELECT RESET Switch failure protection...

Page 18: ...play The new setting value can then be changed by using push buttons If through a new setting another relay characteristic other than the old one has been chosen e g from DEFT to NINV but the time del...

Page 19: ...cedure for forward or backward faults described in chapter 5 2 3 is also valid for the trip ping time of the high set element 5 2 7 Relay characteristic angle RCA The characteristic angle for directio...

Page 20: ...rrents have dropped to 1 xIN within this time CB failure is detected and the related relay activated The CB failure protection function is deactivated again as soon as the phase currents have dropped...

Page 21: ...ignment mode is selected The relays are assigned as follows LEDs I I IE IE are two coloured and light up green when the out put relays are assigned as alarm relays and red as tripping relays In additi...

Page 22: ...R tripping X 1 _ _ _ tI red IE V alarm X _ _ _ 4 IE green tIE V tripping X 1 _ _ _ tIE green IE R alarm X _ _ _ 4 IE red tIE R tripping X 1 _ _ _ tIE red IE V alarm X _ _ _ 4 IE green tIE V tripping X...

Page 23: ...multiplier setting for inverse time overcurrent is a scale factor for the selected characteristics The characteristics for two adjacent relays should have a time interval of about 0 3 0 4 s High set e...

Page 24: ...indicate that it is not a current fault LEDs which were blinking blinking dur ing trip conditions element had picked up just briefly flash If the relay is still in trip condition and not yet reset TR...

Page 25: ...cond part of the soft ware version of the relay e g 4 01 The software version should be quoted in all correspondence Press ing the TRIP button once more the display shows PSW Please enter the correct...

Page 26: ...In By using an RMS metering instrument a greater deviation may be observed if the test current contains harmonics Be cause the MRI1 relay measures only the fundamental component of the input signals...

Page 27: ...o times IS The tripping time may be red from the characteristic curve diagram or calculated with the equations given under technical data Please observe that during the secondary injection test the te...

Page 28: ...directional feature of the relay and the current source is connected to phase 1 current input B3 B4 then the voltage source should be connected to relay terminals A5 A7 In order to test the directiona...

Page 29: ...to red Relay 2 drops and relay 3 responds This test must be repeated for current inputs 12 and 13 In order to determine the direction in the earth current circuit SR version refer to Fig 8 with the ch...

Page 30: ...ng a relay with earth fault directional feature one of the input energizing quantity voltage shall be applied to the relay with a constant value within its ef fective range The other input energizing...

Page 31: ...e current and voltage transformers with the primary side energized Since the cost and poten tial hazards are very high for such a test primary in jection tests are usually limited to very important pr...

Page 32: ...ly 4 x IN Thermal withstand in voltage circuit continuously 1 5 x UN 7 2 Common data Dropout to pickup ratio 97 Returning time 30 ms Time lag error class index E 10 ms Minimum operating time 30 ms Tra...

Page 33: ...01 0 02 0 05 0 1 0 2 5 from set value or 0 3 IN 3 or 20 ms 3 of the measuring value of the current or 20ms see EN60255 3 IE tIE 0 01 15 x IN EXIT 0 03 2 0 s EXIT 0 001 0 002 0 005 0 01 0 02 0 05 0 1 0...

Page 34: ...05 0 01x IN 0 01 0 02 0 05 0 1 x IN 0 01 s 0 02 s 0 05 s 5 from set value or 0 3 IN ER 0 03 IN XR 3 or 15 ms UE UN 100 V 3 PHA e n 1 70 V 1 1 1 120 V UN 230 V 3 PHA e n 2 160 V 1 1 2 300 V UN 400 V 3...

Page 35: ...at I 1 x IN Connection angle 90 Characteristic angle 15 27 38 49 61 72 83 Effective angle 78 related to relay characteristic angle at UN 7 3 9 Determination of earth fault direction MRl1 ER XR Measure...

Page 36: ...5 0 6 0 8 1 0 1 4 Figure 7 2 Extremely Inverse 1 2 3 4 5 6 7 8 910 20 I IS 0 1 1 10 100 1000 t s tI 10 0 8 0 6 0 4 0 3 0 2 0 0 05 0 1 0 2 0 3 0 4 0 5 0 6 0 8 1 0 1 4 Figure 7 3 Very Inverse 1 10 I IN...

Page 37: ...X Rated current 1 A in earth circuits 5 A 1 5 Housing 12TE 19 rack Flush mounting A D RS485 Alternatively with Modbus Protocol M Earth fault current relay with directional feature MRI1 R Earth curren...

Page 38: ...M Combinated time overcurrent and earth fault current relay with earth current directional feature MRI1 I R 3 phase measuring I I Rated current 1 A 5 A 1 5 Phase fault directional feature R Rated vol...

Page 39: ...X X 0 01 x IN E 0 1 IN X WARN TRIP X X X X X X TRIP CHAR IE X X X X X X DEFT tIE V tIE R X X X X X X X X X 0 05 s ER XR 0 04 s others 0s 60 s earth X X X X X X 0 s IE X X X X X X X X X 0 01 x IN E 0 1...

Page 40: ...y 4 Default setting Actual setting Default setting Actual setting Default setting Actual setting Default setting Actual setting I alarm V X tI tripping V X I alarm R X tI tripping R X I alarm V X t tr...

Page 41: ...IE X TCBFP X This technical manual is valid for software version D01 8 10 MRI1 ER IER IRER D20 2 00 MRI1 XR IXR IRXR D24 1 00 MRI1 X IX IXR D00 8 10 MRI1 I E IE IR SR IRE ISR IRSR Modbus Version numbe...

Page 42: ...D 47884 Kempen Germany Telephone 49 0 21 52 145 1 Internet www SEGelectronics de Sales Telephone 49 0 21 52 145 331 Fax 49 0 21 52 145 354 E mail info SEGelectronics de Service Telephone 49 0 21 52 14...

Reviews: