5.4.3  

Fault memory (not for ER/XR types) 

 
When the relay is energized or trips, all fault data are 
stored in a non-volatile memory manner. The 

MRI1

    is 

provided with a fault value recorder for max. eight 
fault occurrences. In the event of additional trippings 
always the oldest data set is written over. 
 
For fault indication not only the trip values are re-
corded but also the status of LEDs. Fault values are in-
dicated when push buttons <-> or <+> are pressed 
during normal measuring value indication. 

• 

Normal measuring values are selected by pressing 
the <SELECT/RESET> button. 

• 

When then the <-> button is pressed, the latest fault 
data set is shown. By repeated pressing the <-> 
button the last but one fault data set is shown etc. 
For indication of fault data sets abbreviations FLT1, 
FLT2, FLT3, ... are displayed (FLT1 means the latest 
fault data set recorded).  

• 

By pressing <SELECT/RESET> the fault measuring 
values can be scrolled. 

• 

By pressing <+> it can be scrolled back to a more 
recent fault data set. At first FLT8, FLT7, ... are al-
ways displayed.When fault recording is indicated 
(FLT1 etc), the LEDs flash in compliance with the 
stored trip information, i.e. those LEDs which 
showed a continuous light when the fault occured 
are now blinking blinking to indicate that it is not a 
current fault. LEDs which were blinking blinking dur-
ing trip conditions, (element had picked up) just 
briefly flash. 

• 

If the relay is still in trip condition and not yet reset 
(TRIP is still displayed), no measuring values can be 
shown. 

• 

To delete the trip store, the push button combina-
tion <SELECT/RESET> and <-> has to be pressed 
for about 3s. The display shows 'wait'. 

 

 

 

Recorded fault values: 

 

Value displayed 

Relevant LED 

Phase currents L1, L2, L3 in I/In  L1, L2, L3 
Earth current I

 in I/I

E

n E 

C.B. switching time in s 

1)

 C.B. 

Expired tripping time of I> 
in % of t

I>

 

2)

 

I> 

Expired tripping time of I

E>

 

in % of t

IE>

 

2)

 

I

E>

 

 
 

1)

  C.B. switching time: 

 

Time between energizing of the trip output relay 

 

and switching of the C.B. (current < 1 % I

N

)). 

 

2)

  Expired tripping time: 

Time between pickup and release of the low set 
element. This value is only displayed for I> and I

E>

 
 

5.5   Reset  

 
Unit 

MRI1

 has the following three possibilities to reset 

thedisplay of the unit as well as the output relay at 
jumper position J3=ON. 
 

Manual Reset

  

• 

Pressing the push button <SELECT/RESET> for some 
time (about 3 s) 

 

Electrical Reset

 

• 

Through applying auxiliary voltage to C8/D8 

 

Software Reset

 

• 

The software reset has the same effect as the 
<SELECT/RESET> push button (see also communica-
tion protocol of RS485 interface). 

 
The display can only be reset when the pickup is not 
present anymore (otherwise "TRIP" remains in display). 
During resetting of the display the parameters are not 
affected. 

Summary of Contents for HighTECH Line

Page 1: ...CTION TECHNOLOGY MADE SIMPLE DIGITAL MULTIFUNCTIONAL RELAY FOR TIME OVERCURRENT PROTECTION HighTECH Line DIGITAL MULTIFUNCTIONAL RELAY FOR TIME OVERCURRENT PROTECTION Revision A Original document Engl...

Page 2: ...for earth fault element tIE 5 2 14 Reset mode for inverse time tripping in earth current path 5 2 15 Current setting for high set element of earth fault supervision IE 5 2 16 Trip delay for high set...

Page 3: ...h fault protection E X Type 7 3 4 Earth fault protection ER XR Type 7 3 5 Switch failure protection 7 3 6 Interface parameter 7 3 7 Inverse time overcurrent protection relay 7 3 8 Direction unit for p...

Page 4: ...e measured values by using dis crete Fourier analysis to suppress the high frequence harmonics and DC components induced by faults or system operations Selectable protective functions between definite...

Page 5: ...the connection has to be realized as per Figure 3 1 and Figure 3 2 Figure 3 3 Phase current measuring and earth current detection by means of Holmgreen circuit This connection can be used with three...

Page 6: ...inally fed to the analog digital converter For the unit type with earth fault directional features ER XR relay type the residual voltage UE in the sec ondary circuit of the voltage transformers is int...

Page 7: ...t MRI1 To prevent that the C B trip coil circuit is interrupted by the MRI1 first i e before interruption by the C B auxiliary contact a dwell time is fixed This setting ensures that the MRI1 remains...

Page 8: ...X soli resi X X X tCBFP X X X X X X X X X X X 50 60 Hz X X X X X X X X X X X LED Flash X X X X X X X X X X X RS485 Slaveaddress X X X X X X X X X X X Baud Rate 3 X X X X X X X X X X X Parity Check 3...

Page 9: ...RESET ENTER TRIP t I I E CHAR I t E I I E tI E EARTH E RS E DISPLAY Figure 3 8 Front panel MRI1 E X SELECT RESET ENTER TRIP t I I CHAR I tI I tI PHASE MRI1 IR L1 L2 L3 RS Q I P I DISPLAY Figure 3 9 F...

Page 10: ...display At pickup trip and parameter setting the green LED lights up to indi cate the forward direction the red LED indicates the reverse direction The LED marked with letters RS lights up during sett...

Page 11: ...induced transients or other system dis turbances The calculated actual current values are compared with the relay settings If a phase current exceeds the pickup value an alarm is given and after the s...

Page 12: ...s at least 2 periods 40 ms at 50 Hz are evaluated For the MRI1 overcurrent relays with directional feature different time delays or time multipliers can be set for forward and backward faults ref to c...

Page 13: ...ing the relay Earth faults beyond the current transformers i e on the consumer or line side will not be detected Figure 4 4 Generator stator earth fault protetion 4 4 2 System earth fault protection W...

Page 14: ...n be measured in three different ways depending on the voltage transformer connec tions refer to Table 4 1 Total current can be measured by connecting the unit either to a ring core C T or to cur rent...

Page 15: ...e current for faulted and non faulted lines in case of compensated systems cos UE residual voltage IE zero sequence current IL inductive component of zero sequence current caused by Petersen coil IC c...

Page 16: ...earthed system are pre dominantly ohmic in character with a small inductive part The characteristic angle for these types of system has therefore been set at 170 in relation to the zero sequence volta...

Page 17: ...E changeover of isolated sin or compensated cos networks for ER XR type SIN COS SELECT RESET Change over of solidly resistance earthed networks SR type SOLI RESI SELECT RESET Switch failure protection...

Page 18: ...play The new setting value can then be changed by using push buttons If through a new setting another relay characteristic other than the old one has been chosen e g from DEFT to NINV but the time del...

Page 19: ...cedure for forward or backward faults described in chapter 5 2 3 is also valid for the trip ping time of the high set element 5 2 7 Relay characteristic angle RCA The characteristic angle for directio...

Page 20: ...rrents have dropped to 1 xIN within this time CB failure is detected and the related relay activated The CB failure protection function is deactivated again as soon as the phase currents have dropped...

Page 21: ...ignment mode is selected The relays are assigned as follows LEDs I I IE IE are two coloured and light up green when the out put relays are assigned as alarm relays and red as tripping relays In additi...

Page 22: ...R tripping X 1 _ _ _ tI red IE V alarm X _ _ _ 4 IE green tIE V tripping X 1 _ _ _ tIE green IE R alarm X _ _ _ 4 IE red tIE R tripping X 1 _ _ _ tIE red IE V alarm X _ _ _ 4 IE green tIE V tripping X...

Page 23: ...multiplier setting for inverse time overcurrent is a scale factor for the selected characteristics The characteristics for two adjacent relays should have a time interval of about 0 3 0 4 s High set e...

Page 24: ...indicate that it is not a current fault LEDs which were blinking blinking dur ing trip conditions element had picked up just briefly flash If the relay is still in trip condition and not yet reset TR...

Page 25: ...cond part of the soft ware version of the relay e g 4 01 The software version should be quoted in all correspondence Press ing the TRIP button once more the display shows PSW Please enter the correct...

Page 26: ...In By using an RMS metering instrument a greater deviation may be observed if the test current contains harmonics Be cause the MRI1 relay measures only the fundamental component of the input signals...

Page 27: ...o times IS The tripping time may be red from the characteristic curve diagram or calculated with the equations given under technical data Please observe that during the secondary injection test the te...

Page 28: ...directional feature of the relay and the current source is connected to phase 1 current input B3 B4 then the voltage source should be connected to relay terminals A5 A7 In order to test the directiona...

Page 29: ...to red Relay 2 drops and relay 3 responds This test must be repeated for current inputs 12 and 13 In order to determine the direction in the earth current circuit SR version refer to Fig 8 with the ch...

Page 30: ...ng a relay with earth fault directional feature one of the input energizing quantity voltage shall be applied to the relay with a constant value within its ef fective range The other input energizing...

Page 31: ...e current and voltage transformers with the primary side energized Since the cost and poten tial hazards are very high for such a test primary in jection tests are usually limited to very important pr...

Page 32: ...ly 4 x IN Thermal withstand in voltage circuit continuously 1 5 x UN 7 2 Common data Dropout to pickup ratio 97 Returning time 30 ms Time lag error class index E 10 ms Minimum operating time 30 ms Tra...

Page 33: ...01 0 02 0 05 0 1 0 2 5 from set value or 0 3 IN 3 or 20 ms 3 of the measuring value of the current or 20ms see EN60255 3 IE tIE 0 01 15 x IN EXIT 0 03 2 0 s EXIT 0 001 0 002 0 005 0 01 0 02 0 05 0 1 0...

Page 34: ...05 0 01x IN 0 01 0 02 0 05 0 1 x IN 0 01 s 0 02 s 0 05 s 5 from set value or 0 3 IN ER 0 03 IN XR 3 or 15 ms UE UN 100 V 3 PHA e n 1 70 V 1 1 1 120 V UN 230 V 3 PHA e n 2 160 V 1 1 2 300 V UN 400 V 3...

Page 35: ...at I 1 x IN Connection angle 90 Characteristic angle 15 27 38 49 61 72 83 Effective angle 78 related to relay characteristic angle at UN 7 3 9 Determination of earth fault direction MRl1 ER XR Measure...

Page 36: ...5 0 6 0 8 1 0 1 4 Figure 7 2 Extremely Inverse 1 2 3 4 5 6 7 8 910 20 I IS 0 1 1 10 100 1000 t s tI 10 0 8 0 6 0 4 0 3 0 2 0 0 05 0 1 0 2 0 3 0 4 0 5 0 6 0 8 1 0 1 4 Figure 7 3 Very Inverse 1 10 I IN...

Page 37: ...X Rated current 1 A in earth circuits 5 A 1 5 Housing 12TE 19 rack Flush mounting A D RS485 Alternatively with Modbus Protocol M Earth fault current relay with directional feature MRI1 R Earth curren...

Page 38: ...M Combinated time overcurrent and earth fault current relay with earth current directional feature MRI1 I R 3 phase measuring I I Rated current 1 A 5 A 1 5 Phase fault directional feature R Rated vol...

Page 39: ...X X 0 01 x IN E 0 1 IN X WARN TRIP X X X X X X TRIP CHAR IE X X X X X X DEFT tIE V tIE R X X X X X X X X X 0 05 s ER XR 0 04 s others 0s 60 s earth X X X X X X 0 s IE X X X X X X X X X 0 01 x IN E 0 1...

Page 40: ...y 4 Default setting Actual setting Default setting Actual setting Default setting Actual setting Default setting Actual setting I alarm V X tI tripping V X I alarm R X tI tripping R X I alarm V X t tr...

Page 41: ...IE X TCBFP X This technical manual is valid for software version D01 8 10 MRI1 ER IER IRER D20 2 00 MRI1 XR IXR IRXR D24 1 00 MRI1 X IX IXR D00 8 10 MRI1 I E IE IR SR IRE ISR IRSR Modbus Version numbe...

Page 42: ...D 47884 Kempen Germany Telephone 49 0 21 52 145 1 Internet www SEGelectronics de Sales Telephone 49 0 21 52 145 331 Fax 49 0 21 52 145 354 E mail info SEGelectronics de Service Telephone 49 0 21 52 14...

Reviews: