background image

TD_MRI1_06.05_GB 

23 

5.3   Setting value calculation 

 

5.3.1  

Definite time overcurrent element 

 

Low set element I>

 

The pickup current setting is determined by the load 
capacity of the protected object and by the smallest 
fault current within the operating range. The pickup 
current is usually selected about 20% for power lines, 
about 50% for transformers and motors above the 
maximum expected load currents. 
 
The delay of the trip signal is selected with considera-
tion to the demand on the selectivity according to sys-
tem time grading and overload capacity of the pro-
tected object. 
 

High set element I>> 

The high set element is normally set to act for near-by 
faults. A very good protective reach can be achieved 
if the impedance of the protected object results in a 
well-defined fault current. In case of a line-transformer 
combination the setting values of the high set element 
can even be set for the fault inside the transformer. 
The time delay for high set element is always inde-
pendent to the fault current. 
 
 

5.3.2  

Inverse time overcurrent  

 element 

 
Beside the selection of the time current characteristic 
one set value each for the phase current path and 
earth current path is adjusted. 

Low set element I>

 

The pickup current is determined according to the 
maximum expected load current. For example: 
Current transformer ratio: 400/5A 
Maximum expected load current: 300A 
Overload coefficient: 1.2 (assumed) 
Starting current setting: 
Is = (300/400) x 1.2 = 0.9 x I

N

 

Time multiplier setting

 

The time multiplier setting for inverse time overcurrent is 
a scale factor for the selected characteristics. The 
characteristics for two adjacent relays should have a 
time interval of about 0.3 - 0.4 s. 

High set element I>>

 

The high set current setting is set as a multiplier of the 
nominal current. The time delay tI>> is always inde-
pendent to the fault current. 

5.4    Indication of measuring and fault  
 values 

 

5.4.1  

Indication of measuring values 

 
The following measuring quantities can be indicated 
on the display during normal service: 

• 

Apparent current in phase 1 (LED L1 green) 

• 

Active current in Phase 1 (LED L1 and I

P

 green) * 

• 

Reactive current in Phase 1 (LED L1 and I

Q

 green)* 

• 

Apparent current in phase 2 (LED L2 green) 

• 

Active current in Phase 2 (LED L2 and I

P

 green) * 

• 

Reactive current in Phase 2 (LED L2 and I

Q

 green)* 

• 

Apparent current in phase 3 (LED L3 green) 

• 

Active current in Phase 3 (LED L3 and I

P

 green) * 

• 

Reactive current in Phase 3 (LED L3 and I

Q

 green)* 

• 

Apparent earth current (LED E green) 

• 

Active earth current (LED E and I

P

 green) * 

• 

Reactive earth current (LED E and I

Q

 green) * 

• 

Residual voltage UR (LED U

E

) only at ER/XR-relay 

type 

• 

Angle between I

E

 and U

E

 

* only in case that the directional option is built in. 
 
The indicated current measuring values refer to nomi-
nal current. (For 

MRI1-XR/X

 relays the indicated 

measuring values refer to % of I

N

 
 

5.4.2  

Indication of fault data 

 
All faults detected by the relay are indicated on the 
front plate optically. For this purpose, the four LEDs (L1, 
L2, L3, E) and the four function LEDs (I>, I>>, IE>, 
IE>> and 

→←

) are equipped at 

MRI1

. If, for example 

an overcurrent occurs, first the corresponding phases 
will light up. LED I> lights up at the same time. After 
tripping the LEDs are lit permanently. 
 
 
 

Summary of Contents for HighTECH Line

Page 1: ...CTION TECHNOLOGY MADE SIMPLE DIGITAL MULTIFUNCTIONAL RELAY FOR TIME OVERCURRENT PROTECTION HighTECH Line DIGITAL MULTIFUNCTIONAL RELAY FOR TIME OVERCURRENT PROTECTION Revision A Original document Engl...

Page 2: ...for earth fault element tIE 5 2 14 Reset mode for inverse time tripping in earth current path 5 2 15 Current setting for high set element of earth fault supervision IE 5 2 16 Trip delay for high set...

Page 3: ...h fault protection E X Type 7 3 4 Earth fault protection ER XR Type 7 3 5 Switch failure protection 7 3 6 Interface parameter 7 3 7 Inverse time overcurrent protection relay 7 3 8 Direction unit for p...

Page 4: ...e measured values by using dis crete Fourier analysis to suppress the high frequence harmonics and DC components induced by faults or system operations Selectable protective functions between definite...

Page 5: ...the connection has to be realized as per Figure 3 1 and Figure 3 2 Figure 3 3 Phase current measuring and earth current detection by means of Holmgreen circuit This connection can be used with three...

Page 6: ...inally fed to the analog digital converter For the unit type with earth fault directional features ER XR relay type the residual voltage UE in the sec ondary circuit of the voltage transformers is int...

Page 7: ...t MRI1 To prevent that the C B trip coil circuit is interrupted by the MRI1 first i e before interruption by the C B auxiliary contact a dwell time is fixed This setting ensures that the MRI1 remains...

Page 8: ...X soli resi X X X tCBFP X X X X X X X X X X X 50 60 Hz X X X X X X X X X X X LED Flash X X X X X X X X X X X RS485 Slaveaddress X X X X X X X X X X X Baud Rate 3 X X X X X X X X X X X Parity Check 3...

Page 9: ...RESET ENTER TRIP t I I E CHAR I t E I I E tI E EARTH E RS E DISPLAY Figure 3 8 Front panel MRI1 E X SELECT RESET ENTER TRIP t I I CHAR I tI I tI PHASE MRI1 IR L1 L2 L3 RS Q I P I DISPLAY Figure 3 9 F...

Page 10: ...display At pickup trip and parameter setting the green LED lights up to indi cate the forward direction the red LED indicates the reverse direction The LED marked with letters RS lights up during sett...

Page 11: ...induced transients or other system dis turbances The calculated actual current values are compared with the relay settings If a phase current exceeds the pickup value an alarm is given and after the s...

Page 12: ...s at least 2 periods 40 ms at 50 Hz are evaluated For the MRI1 overcurrent relays with directional feature different time delays or time multipliers can be set for forward and backward faults ref to c...

Page 13: ...ing the relay Earth faults beyond the current transformers i e on the consumer or line side will not be detected Figure 4 4 Generator stator earth fault protetion 4 4 2 System earth fault protection W...

Page 14: ...n be measured in three different ways depending on the voltage transformer connec tions refer to Table 4 1 Total current can be measured by connecting the unit either to a ring core C T or to cur rent...

Page 15: ...e current for faulted and non faulted lines in case of compensated systems cos UE residual voltage IE zero sequence current IL inductive component of zero sequence current caused by Petersen coil IC c...

Page 16: ...earthed system are pre dominantly ohmic in character with a small inductive part The characteristic angle for these types of system has therefore been set at 170 in relation to the zero sequence volta...

Page 17: ...E changeover of isolated sin or compensated cos networks for ER XR type SIN COS SELECT RESET Change over of solidly resistance earthed networks SR type SOLI RESI SELECT RESET Switch failure protection...

Page 18: ...play The new setting value can then be changed by using push buttons If through a new setting another relay characteristic other than the old one has been chosen e g from DEFT to NINV but the time del...

Page 19: ...cedure for forward or backward faults described in chapter 5 2 3 is also valid for the trip ping time of the high set element 5 2 7 Relay characteristic angle RCA The characteristic angle for directio...

Page 20: ...rrents have dropped to 1 xIN within this time CB failure is detected and the related relay activated The CB failure protection function is deactivated again as soon as the phase currents have dropped...

Page 21: ...ignment mode is selected The relays are assigned as follows LEDs I I IE IE are two coloured and light up green when the out put relays are assigned as alarm relays and red as tripping relays In additi...

Page 22: ...R tripping X 1 _ _ _ tI red IE V alarm X _ _ _ 4 IE green tIE V tripping X 1 _ _ _ tIE green IE R alarm X _ _ _ 4 IE red tIE R tripping X 1 _ _ _ tIE red IE V alarm X _ _ _ 4 IE green tIE V tripping X...

Page 23: ...multiplier setting for inverse time overcurrent is a scale factor for the selected characteristics The characteristics for two adjacent relays should have a time interval of about 0 3 0 4 s High set e...

Page 24: ...indicate that it is not a current fault LEDs which were blinking blinking dur ing trip conditions element had picked up just briefly flash If the relay is still in trip condition and not yet reset TR...

Page 25: ...cond part of the soft ware version of the relay e g 4 01 The software version should be quoted in all correspondence Press ing the TRIP button once more the display shows PSW Please enter the correct...

Page 26: ...In By using an RMS metering instrument a greater deviation may be observed if the test current contains harmonics Be cause the MRI1 relay measures only the fundamental component of the input signals...

Page 27: ...o times IS The tripping time may be red from the characteristic curve diagram or calculated with the equations given under technical data Please observe that during the secondary injection test the te...

Page 28: ...directional feature of the relay and the current source is connected to phase 1 current input B3 B4 then the voltage source should be connected to relay terminals A5 A7 In order to test the directiona...

Page 29: ...to red Relay 2 drops and relay 3 responds This test must be repeated for current inputs 12 and 13 In order to determine the direction in the earth current circuit SR version refer to Fig 8 with the ch...

Page 30: ...ng a relay with earth fault directional feature one of the input energizing quantity voltage shall be applied to the relay with a constant value within its ef fective range The other input energizing...

Page 31: ...e current and voltage transformers with the primary side energized Since the cost and poten tial hazards are very high for such a test primary in jection tests are usually limited to very important pr...

Page 32: ...ly 4 x IN Thermal withstand in voltage circuit continuously 1 5 x UN 7 2 Common data Dropout to pickup ratio 97 Returning time 30 ms Time lag error class index E 10 ms Minimum operating time 30 ms Tra...

Page 33: ...01 0 02 0 05 0 1 0 2 5 from set value or 0 3 IN 3 or 20 ms 3 of the measuring value of the current or 20ms see EN60255 3 IE tIE 0 01 15 x IN EXIT 0 03 2 0 s EXIT 0 001 0 002 0 005 0 01 0 02 0 05 0 1 0...

Page 34: ...05 0 01x IN 0 01 0 02 0 05 0 1 x IN 0 01 s 0 02 s 0 05 s 5 from set value or 0 3 IN ER 0 03 IN XR 3 or 15 ms UE UN 100 V 3 PHA e n 1 70 V 1 1 1 120 V UN 230 V 3 PHA e n 2 160 V 1 1 2 300 V UN 400 V 3...

Page 35: ...at I 1 x IN Connection angle 90 Characteristic angle 15 27 38 49 61 72 83 Effective angle 78 related to relay characteristic angle at UN 7 3 9 Determination of earth fault direction MRl1 ER XR Measure...

Page 36: ...5 0 6 0 8 1 0 1 4 Figure 7 2 Extremely Inverse 1 2 3 4 5 6 7 8 910 20 I IS 0 1 1 10 100 1000 t s tI 10 0 8 0 6 0 4 0 3 0 2 0 0 05 0 1 0 2 0 3 0 4 0 5 0 6 0 8 1 0 1 4 Figure 7 3 Very Inverse 1 10 I IN...

Page 37: ...X Rated current 1 A in earth circuits 5 A 1 5 Housing 12TE 19 rack Flush mounting A D RS485 Alternatively with Modbus Protocol M Earth fault current relay with directional feature MRI1 R Earth curren...

Page 38: ...M Combinated time overcurrent and earth fault current relay with earth current directional feature MRI1 I R 3 phase measuring I I Rated current 1 A 5 A 1 5 Phase fault directional feature R Rated vol...

Page 39: ...X X 0 01 x IN E 0 1 IN X WARN TRIP X X X X X X TRIP CHAR IE X X X X X X DEFT tIE V tIE R X X X X X X X X X 0 05 s ER XR 0 04 s others 0s 60 s earth X X X X X X 0 s IE X X X X X X X X X 0 01 x IN E 0 1...

Page 40: ...y 4 Default setting Actual setting Default setting Actual setting Default setting Actual setting Default setting Actual setting I alarm V X tI tripping V X I alarm R X tI tripping R X I alarm V X t tr...

Page 41: ...IE X TCBFP X This technical manual is valid for software version D01 8 10 MRI1 ER IER IRER D20 2 00 MRI1 XR IXR IRXR D24 1 00 MRI1 X IX IXR D00 8 10 MRI1 I E IE IR SR IRE ISR IRSR Modbus Version numbe...

Page 42: ...D 47884 Kempen Germany Telephone 49 0 21 52 145 1 Internet www SEGelectronics de Sales Telephone 49 0 21 52 145 331 Fax 49 0 21 52 145 354 E mail info SEGelectronics de Service Telephone 49 0 21 52 14...

Reviews: