Page system informations:
1 : Indicates the serial number of the device
2 : Indicates the software version of the central unit card.
3 : Indicates the software version of the user interface card.
4 : Indicates the name of the device.
5 : Indicates the current protection level.
6 : If press this area : go back to page menu.
7 : If press this area : go back to main page.
RUNNING :
Conditions to start declogging cycle :
-
Input I1=1 (input closed)
-
Running order dP ON (if cycle is dependent on load loss measure dP).
If detection of fan stop, by input I1 :
-
If we lose the input I1 (I1=0), fan stop is observed : the sequencer executes the defined number of cycles
and stops. If the defined number of cycles is at 0 : the sequencer stops immediately or finishes the running
cycle, according to the choosen mode.
If detection of fan stop, by load loss measure dP :
-
If we lose the input I1 (I1=0), the sequencer stops immediately or finishes the running cycle, according to
the choosen mode.
-
If detection of fan stop : the sequencer executes the defined number of cycles and stops. If the defined
number of cycles is at 0 : the sequencer stops immediately or finishes the running cycle, according to the
choosen mode.
Note : when the device is switched on, a temporization of 10 seconds prohibits declogging cycle.