SEFRAM SEQUENCER SET18DP Manual Download Page 17

 

SEQUENCER WITH 

DIFFERENTIAL PRESSURE 

SWITCH

 

 

 

Technical brochure              

  FI 72.0452.0617E 

 

   Page 17 / 25 

 

Page parameters 1/4: 

 

1 : T1 : pulse time on one declogging SV. 
     Adjustable from 3 to 255 1/100th seconds (reachable at level 1 or above). 
 
2 : T2 : rest time between two pulses of declogging SV. 
     Adjustable from 1 to 255 seconds (reachable at level 1 and above ). 
 
3 : T2A : second rest between two pulses of declogging SV. 
     T2A time  (shorter than T2)  replaces T2 time if accelerated running (pressure>threshold T2A).  
     Adjustable from 1 to 255 seconds (reachable at level 1 and above ). 
      
4 : T3 : rest time between two declogging cycles. 
     Adjustable from 0 to 255 minutes (reachable at level 1 and above). If adjusted to 0 : not active. 
      
5 : T4 : maximum time without declogging cycle. 
     If the device did not have any declogging cycle for the quantity of hours which is adjusted, the ongoing cycle is stopped 
    (if stop in cycle) and a declogging cycle is launched. 
     Remark: T4 time is reset at each pulse on any SV. 
     Adjustable from 0 to 255 hours( reachable at level 1 and above ). If adjusted to 0 : not active. 
      
6 : Quantity of declogging SV.  
     Adjustable from 1 to 18, according to the quantity of SV which are connected (reachable at level 1 and above). 
      
7 : Adjustment of the type of declogging stop, in case we lose the running order : 
      « End of cycle » : the ongoing cycle ends up. 
      « On cycle » : cycle stops during its running (at the SV where cycle is, at the end of the T2 time). It will start 
      again where it was. (reachable at level 1 and above).  
      
8 : Condition to let the declogging cycle, linked to T4 time, runs.  
     Two possible choices : « whatever input I1 » or « if I1 Input=1 »  
       
9 : Display of ongoing protection level. 

 

10 : If press this area : go back to page menu. 
11 : If press this area : go back to main page. 
12 : If press this area :  goes to the next adjustments page. 
 

10 

11 

12 

Summary of Contents for SEQUENCER SET18DP

Page 1: ...echnical brochure FI 72 0452 0617E Page 1 25 Outputs SV AC version PLACE GUTENBERG 59175 TEMPLEMARS France Tel 33 0 3 20 60 49 49 Fax 33 0 3 20 95 59 62 Email contact sefram eu Web www sefram eu Elect...

Page 2: ...ice thanks to a graphic colour touch screen Interface is multilingual Evolution of the declogging cycle the running defaults and the pressure loss measure are clearly displayed and detailed A graphic...

Page 3: ...3 100th to 255 100th of a second Time T2 T2A idle between 2 outputs 1 255 seconds Time T3 rest time between 2 cycles 0 255 minutes Time T4 automatic dust removal cycle 0 255 hours Number of cycles if...

Page 4: ...4 25 DIMENSION AND MOUNTING dirty air side clean air side Connection for pipe 6 8mm Tightening capacity of glands ISO 16 From 4 to 8mm ISO 20 From 7 5 to13mm ISO 20b From9 5 to 15mm If version till 1...

Page 5: ...hure FI 72 0452 0617E Page 5 25 dirty air side clean air side Connection for pipe 6 8mm Tightening capacity of glands ISO 16 from 4 to 8mm ISO 20 from 7 5 to13 mm If version till 10 SV by individual c...

Page 6: ...factory answering the ordered version warning the device must be switched off Remarks The supply choices 115V 230V or 24 48V can be made only with order If supply voltage 115V 230V the voltage choice...

Page 7: ...230VAC 24VAC 230VAC 48VAC 115VAC 24VAC 115VAC 48VAC WARNING a modification of the supply voltage and or the solenoid valves voltage requires to update the descriptive label placed outside of the box J...

Page 8: ...t of the box According to configuration of the device some terminals may not be included Cable strings will be flexible and will have a section between 0 5 and 1 5 mm2 If version till 18 SV with multi...

Page 9: ...l 10 SV with individual cable 1 common ground for each SV Supply Depending on the version 115V 230V 24V 48V 50 60Hz Connection of outputs Solenoid valves 1 to 10 Output 4 20mA for register indicator e...

Page 10: ...menu is displayed To activate a function or access to adjustment of a parameter press the corresponding area Remark after 30 seconds without any action main menu is automatically displayed unless dP m...

Page 11: ...ted to 0 value 5 Display of Low Alarm dP Gray if measure is above the Low Alarm threshold Red if measure is below the Low Alarm threshold Remarks Low Alarm has a delay of 5 seconds Low Alarm is not ac...

Page 12: ...to 0 this one will not be displayed 2 If press this area go back to main page 3 Display of measure values of load loss dP mini and maxi which are observed Remarks The mini value is observed two minute...

Page 13: ...r 5 Counter of cycles done manufacturer 6 If press this area return to main page 7 Displays the current protection level 8 Reachable only at level 1 If press this area the counter number of user cycle...

Page 14: ...this area go back to main page 2 If press this area jump to page safety 3 If press this area jump to page language 4 If press this area jump to page adjustments 5 If press this area jump to page syste...

Page 15: ...Page language 1 If press this area changes to English language and jumps to main page 2 If press this area changes to French language and jump to main page 3 If press this area go back to page menu 4...

Page 16: ...anufacturer This level gives access to all possibilities of level 1 with also the possibility to reset some counters for instance 1 If press this area request password According to the password entere...

Page 17: ...ty of hours which is adjusted the ongoing cycle is stopped if stop in cycle and a declogging cycle is launched Remark T4 time is reset at each pulse on any SV Adjustable from 0 to 255 hours reachable...

Page 18: ...ld T2A is adjusted to 0 the function is not active always in normal running 5 Threshold High Alarm dP reachable at level 1 or above If measure dP is above this threshold more than 5 seconds High Alarm...

Page 19: ...mark the running of the fan is detected if input I1 1 by dP loss the stop of the fan is detected if the load loss measure is lower than the value indicated on the next parameter see point 2 Remark the...

Page 20: ...he load loss measure dP 0 daPa The output is at 20mA if the load loss measure dP indicated value Between 4 and 20 mA the output is linear and proportional to the load loss measure dP 1 Adjust the valu...

Page 21: ...running without taking into consideration the input I1 or the load loss measure dP The value countdowns according to the cycles which are achieved 2 Choose the SV to activate manually 3 If press this...

Page 22: ...detection of fan stop by input I1 If we lose the input I1 I1 0 fan stop is observed the sequencer executes the defined number of cycles and stops If the defined number of cycles is at 0 the sequencer...

Page 23: ...ult will generate the display of the potential following fault RELAY OUTPUT The relay is supplied electricity if there is no alarm and no fault contact between terminals identified C and NO The relay...

Page 24: ...ral regimes TT TN or IT Nevertheless we recommend that the device is supplied through the intermediary of an insulation transformer for which the primary is supplied between phases and not between pha...

Page 25: ...the device apart from the connections In case of failure no action is permitted and the unit must be returned to the following address CERTIFICATE The SET18DP respects the European directives CEM BT...