MAGIQTOUCH BMS INDUSTRIAL CONTROLLER - MANUAL
|
13
ELECTRICAL INSTALLATION cont.
INPUTS SIGNALS - DIGITAL
SIG
GND
COOL INPUT
SIG
GND
SIG
GND
SYSTEM
ON INPUT
SET
F
A
N
SPEED
INPUT
PWR /
ERROR CODE
+12VDC
0VDC
POWER
INPUT
BMS INDUSTRIAL CONTROLLER M1
BMS INDUSTRIAL CONTROLLER MS1
ILL2482-A
ILL2482-A
Name
Label Function
Low
High
Input Type
On/Off
SYSTEM
ON
INPUT
Master mode only: Turn Cooler
On or Off
Cooler Off
Cooler On Digital 10Vdc
Slave mode only: Switch
operation between Wall control
and BMS
MagIQtouch
Control
BMS
Control
Digital 10Vdc
Operation Mode
COOL
INPUT
Cool or Vent
Fan Only
Cool
Mode
Digital 10Vdc
Fan Speed
SET FAN
SPEED
INPUT
Set speed from 1-10
N/A
N/A
Analogue
0 - 10Vdc
Logical Level Min
Typ.
Max
Unit
Low
0
2
Vdc
High
4
10
12
Vdc
Recommended voltage level for digital inputs.