Terminate the power cable in a junction box installed nearby.
The fixed wiring must be fitted with an isolation switch that
breaks the active (hot) and neutral (common) in accordance
with local wiring rules. We recommend the junction box be
located and installed on the duct.
Do not penetrate the duct near the Weatherseal.
AUSTRALIA ONLY
A 10A GPO within one metre of the dropper’s cable exit hole is
required.
ILL3102-A
Installation of the cooler must conform to local electrical rules,
regulations and standards.
.
Important!
It is a requirement of Seeley International that all
coolers be connected to a dedicated circuit to the distribution
board, with a separate circuit breaker and incorporate a separate
isolation switch in accordance with the local wiring rules.
The following specifications for the cooler electrical supply
are required:
220 - 240V / 50 or 60Hz Single Phase. (See
nameplate for exact data in cooler)
The electronics module is fitted with a replaceable 10A anti-
surge fuse and an isolation switch that is toggled manually.
WARNING!
Replacing the fuse exposes the operator to high
voltage components. This operation may only be conducted
by a qualified electrician. To replace the fuse: turn off the main
isolator to the cooler, turn off the electronics isolation switch,
remove the electronics cover and replace the fuse.
WARNING!
If the supply cord is damaged, it must be replaced
by the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Note!
The maximum length for the wall control cable to travel
alongside the power cable is 10m (33’)