16
|
COMMISSIONING THE COOLER
TESTING THE PUMP
Test the pump by turning the cooler on at the controller, in
“COOL” mode. Check that water is evenly distributed to all
pads.
Note!
If the cooler has not been on before it will run a “Pre-Wet”
routine where the pump will operate to saturate the pads.
This cycle takes 2 minutes, then the fan will start automatically.
TESTING THE DRAIN VALVE
Select the “SETTINGS” mode on the MagIQtouch Controller
and select the “COOLER” sub-heading. Select the “MANUAL
DRAIN” option to operate and test the drain valve.
ILL1664-A
Within the SETTINGS menu of the MagIQtouch Controller is the
COOLER sub-heading. Here various settings of the cooler can
be adjusted.
About Appliance
Displays information such as model number, serial number and
software version for all coolers connected to the controller.
Night Quiet Mode
Restricts fan speed to a specified level during a specified night
period.
Manual Drain
Turns cooler off and drains the pan (reservoir).
Pad Flush
Turns cooler off and runs pump for a specified amount of time.
Auto Restart
By turning this option to ‘ON’, the cooler will automatically
restart after a power failure.
Drain and Dry
Cooler will drain and fan will run for 1 hour every day at a
specified time.
Water Manager
Select the preferred water management method:
• Salinity Measurement - replaces water when salinity level
reaches set point.
•
Timed Drain - drains the pan (reservoir) after 8 pan (reservoir)
fill cycles or every
65 minutes (system dependant).
• No Drain Control - salinity control external to electronics eg.
continuous bleed.
• No Water Thermostatic - allows thermostatic control in VENT
mode. No water present. Cooling performance is limited.
Pre-wet
When COOL mode is activated, the pump will run for 90
seconds before the fan is switched on.
Salinity Level
Sets the salinity level at which the pan (reservoir) will drain in
“SALINITY MEASUREMENT” mode.
Tank (Pan) Drain Delay
Sets the time delay before the drain valve opens after the pump
in the cooler is turned off.
Autostart
Automatically restarts the cooler in the last operating mode after
a power outage.
ILL1664-A