CEILING INSTALLATION

Heater platform and clearances

  The heater must be mounted on a platform to enable access for  

  servicing and maintenance.

  Minimum clearances must be maintained around the heater as   

 shown.

  A 600mm wide walkway must be provided from the ceiling  

 

  access point to the appliance.

  Permanent artificial lighting must be provided at the appliance    

  with the switch adjacent to the access opening.

  Check that the section of the roof in which the heater is to be    

  installed is capable of supporting the additional load of the  

 

  heater. Where possible, the heater should be mounted over a    

  load-bearing wall so that it is not being supported by the ceiling   

  joists alone.

  Check that the heater does not cause deformation of any part of  

  the building structure.

Flue connection - TQ3, TQ4, TQM5, TQS3, TQS4

  This heater must be flued using AGA approved 100 mm metal   

  flue pipe.

  External joins - socket must face downwards. Internal joins -    

  socket must face upwards.

  Socket joins must be adequately sealed - eg, Silastic 747 silicone  

 sealant.

  Twin-wall metal flue must be used for any part of the flue that is   

  not readily accessible.

  Twin-wall metal flue is recommended for flue exceeding 2m in    

 length.

Flue lengths: 

 

 

Flue bends: 

 

   - Maximum vertical: 4.8m   

 - Maximum 2 x 90

o

 elbows

   - Maximum horizontal: 4m  

 - 2 x 45o bends = 1 x 90

elbow

   - Maximum total: 6m

Permanent Platform

19 mm particle board

or equivalent

500 mm to nearest

part of roof

200 mm minimum

for servicing

Fire resistant base NOT REQUIRED

100 mm flue cowl

AGA approved

100 mm 90

o

bend

100 mm flue pipe

Single or twin skin

AGA approved

HX END 

OF HEATER

ROOM FAN

 END OF

 HEATER

Ensure 200mm minimum clearance above heater

Service/maintenance platform - 19mm particle board or equivalent

HEATER LOCATION

AVOID QUIET AREAS:

- Above bedrooms, living room,

  lounge room, dining room etc

PREFERRED LOCATIONS:

- Above laundry, bathroom,

  kitchen, garage etc’

Flue

E

A

 

A = 385 or 510

 

Depends on model.

 

See page 9.

 

E = 770, 880,1160 

 

Depends on model - see

   “Heater Dimensions” page

750 Min

Gas

supply

Isolation

valve

750 Min

 90

o

 bend and starter collars are included in internal installation    

  accessories kit.

  Larger starter collars (400mm) required for the X30,X32 & 35kW  

  units are supplied inside the heater fan inlet.

Fit flue socket 

to heater

Fitting the flue

Fit flue elbow 

inside socket 

on heater

Fit flue pipe 

inside socket 

on flue elbow

SEAL CONNECTIONS: Seal flue and condensate drain connections using 

silicone sealant or 

PVC primer and solvent cement.

INSULATE DRAIN LINE: Fit insulation (eg, Armaflex) over full length of condensate drain line in sub-zero climates

Minimum 500mm to 

nearest part of roof

100mm plastic 

DWV vent cowl

100mm plastic 

DWV pipe

100mm plastic 

DWV M-F elbow

200mm minimum for 

maintenance and servicing 

access

Vent cowl, condensate drain tee assembly, 

flue drain elbow and flue drain hose are 

supplied in internal installation accessories kit. 

Terminate condensate drain 

in a suitable location

Remove & discard flue 

transit plug & one drain 

transit plug

Fix flue elbow in place 

with screw

Condensate drain tee

assembly

Flue drain elbow

Flue drain hose

Secure condensate drain to 

flexible tube using hose 

clamp supplied

Flue & condensate drain connection

Condensate drain tee assembly:

The flexible tube supplied as part of the condensate drain tee assembly is intended to prevent excessive strain of the condensate drain fittings when 

fitting and securing the rigid PVC drain line. It is not designed to take the place of a 90

o

 bend. 

Seal remaining drain transit plug located on the opposite side of the heater to

 condensate drain using silicone sealant or PVC primer and solvent cement.

11

TQ3, TQ4, TQ5, TQM5, TQM6, TQS3, TQS4, TQS5, TQS6

Summary of Contents for Braemar Ecostar TQ3

Page 1: ...Braemar Ecostar TQ3 TQ4 TQ5 TQM5 and TQM6 Gas Ducted Heater Braemar Supernova TQS3 TQS4 TQS5 and TQS6 Gas Ducted Heater INSTALLATION MANUAL ...

Page 2: ...1 TQ3 TQ4 TQ5 TQM5 TQM6 TQS3 TQS4 TQS5 TQS6 ...

Page 3: ...guide to contractors and employees to assist in minimising risk Risk Assessment A risk assessment of all hazardous tasks is required under legislation A risk assessment is an essential element that should be conducted before the commencement of work to identify and eliminate the risk of falls and other risks or to minimise these risks by implementing control measures This does not need to be a com...

Page 4: ...ng loom at the plug near the top of the centre panels Disconnect the combustion fan suction hose connected to pressure switches or hose connector depending on heater model Disconnect the ignition lead flame sense lead and flame rollout lead from the ICS PCB and feed through the grommet in the centre panel This is easiest to do with the grommet removed from the panel Remove the two retaining screws...

Page 5: ...s via a 24Vac relay to switch the cooling system on and off A MagIQ link module is required to connect the Braemar Invertair inverter add on cooling system to the heater Ensure ADD ON COOLER and GAS DUCTED HEATER is selected at the Appliance types screen during system setup on the MagIQtouch Controller to enable the system to operate the Braemar add on cooling system 4 Fit side panels back to heat...

Page 6: ...nstalled in the floor should discharge sideways Registers installed in the ceiling should discharge predominantly vertically 1 Based on standard 100 x 300mm floor outlets and 150mm round ceiling outlets 2 Minimum outlets open to achieve optimum turndown performance 3 X in model refers to extra air models maximum outlets will be reduced when a add on cooling coil is installed Additional notes For h...

Page 7: ...uch Controller Master MagIQtouch Air Sensor systems ensure that the COMMON zone is always heated even if it is only a small air flow The common zone must include a return air grille Explain to the customer the function of the return air duct and the need for a clear air path to the return air grille air cannot travel through closed doors DO NOT in any way obstruct the flow of return air For Single...

Page 8: ...h a separate circuit breaker Wiring must be installed in accordance with the relevant electrical standards regulations The electrical supply must be 240V 50Hz A conventional 10A 3 pin 240V GPO must be fitted adjacent to the heater Ensure that the polarity of the power supply is correct If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified pe...

Page 9: ...079073 077420 TQM5X30 NA NA NA 075006 075556 075556 094939 094922 075587 094328 076898 076362 076386 079073 077420 TQ516 NA NA NA 075525 075532 075525 094939 094922 075587 094328 076898 075990 076034 NA NA TQ523 NA NA NA 075525 075532 075525 094939 094922 075587 094328 076898 075990 076034 NA NA TQ5X23 NA NA NA 075525 075532 075525 094939 094922 075587 094328 076898 075990 076034 NA NA TQ532 NA NA...

Page 10: ... 400 555 330 687 609 83 TQ3X20 TQ4X20 385 660 574 25 770 202 383 735 415 244 350 555 332 695 625 55 TQ3X25 TQ4X25 385 660 574 25 770 202 383 735 415 244 350 555 332 695 625 55 TQ3X30 TQ4X30 510 660 557 25 880 200 415 767 415 240 400 555 330 687 609 83 TQ516 385 660 574 25 1150 535 765 1067 395 244 300 578 670 1003 625 55 TQ523 385 660 574 25 1150 535 765 1067 395 244 300 578 670 1003 625 55 TQ532 ...

Page 11: ...le location Fix flue in place with screw Remove discard lower transit plug Check that upper transit plug is secure External flue terminal External flue terminal stainless steel Fix in place with screw Heater flue outlet spigot A flue terminal and condensate drain elbow are supplied in TQM TQS6 external installation accessories kit P No 075570 Heaters Heaters Heaters Heaters TQ516 TQ523 TQ5X23 TQ53...

Page 12: ...OOM FAN END OF HEATER Ensure 200mm minimum clearance above heater Service maintenance platform 19mm particle board or equivalent HEATER LOCATION AVOID QUIET AREAS Above bedrooms living room lounge room dining room etc PREFERRED LOCATIONS Above laundry bathroom kitchen garage etc Flue E A A 385 or 510 Depends on model See page 9 E 770 880 1160 Depends on model see Heater Dimensions page 750 Min Gas...

Page 13: ...embly Flue drain elbow Vent cowl Flue drain hose SEAL CONNECTIONS Seal flue and condensate drain connections using silicone sealant or PVC primer and solvent cement INSULATE DRAIN LINE Fit insulation eg Armaflex over full length of condensate drain line in sub zero climates FLOOR concrete base DUCT HEATER FLUE External Wall 200mm minimum for servicing Flue to terminate outside building Light switc...

Page 14: ...f a downpipe via a tundish Condensate drain must run down hill from connection point on heater to point of discharge do not allow any part to run up hill Condensate drain must be well supported Do not allow condensate to be discharged into any potable water system or potable water system collection point Fit insulation eg Armaflex over full length of condensate drain line in sub zero climates INST...

Page 15: ...switch to LOW and check pressure at outlet test point All natural gas models 400 20 Pa 450 20 Pa for TQ435 Propane models TQ4 15 20 25 1100 100Pa TQ430 1000 100Pa TQ516 1100 100Pa TQ23 32 800 100Pa OUTLET PRESSURE TEST POINT REGULATOR ADJUSTMENT COVER OUTLET PRESSURE TEST POINT LOW PRESSURE ADJUSTMENT HIGH PRESSURE ADJUSTMENT Gas Out Gas Out COMMISSIONING INSTALLER OR COMMISSIONING AGENT Installat...

Page 16: ...S6 Heaters Before turning the MagIQtouch Controller on ensure all components have been connected to the system It is very important when stepping through the Wall Control system installation wizard that you follow each prompt carefully to ensure that the system is configured correctly NOTE if you have multiple evaporative coolers refer cooler installation manual ADJUSTING MAXIMUM FAN SPEEDS AFTER ...

Page 17: ...as supply Min supply pressure 1 13 kPa NG Has gas meter been installed Turn gas on at gas meter Controller not connected Connect manual 2 wire thermostat to MANUAL T STAT terminals on ICS Connect MagIQtouch Controller to WALL CONTROL terminals on ICS No Controller communication Refer to System Setup section of this manual MagIQtouch Controller not calling for heat Adjust set point above current ro...

Page 18: ...ly voltage out of range L2 23 Room fan not running L2 24 Room fan running backwards L1 25 Condensate wiring FLAG incorrect L1 26 Gas rates wiring FLAG incorrect L1 27 Thermistor wiring FLAG incorrect L1 28 Modulating wiring FLAG incorrect L1 30 Loom ID incorrect L1 31 Combustion air pressure prior to start L1 32 Combustion air pressure too low at start L2 33 Gas relay High error L2 34 Gas relay Lo...

Page 19: ......

Page 20: ...ational com It is the policy of Seeley International to introduce continual product improvement Accordingly specifications are subject to change without notice Please consult with your dealer to confirm the specifications of the model selected www braemar com au ...

Reviews: