2.6  MOUNTING THE HANDLE TO THE PLASTIC BASE 

Reinstall the handle on to the base by using the two large flathead Phillips screws.  You will be 
later sliding a plastic plaque into the handle but don’t do this yet.  You will first need to wire the 
unit and then adjust the sensitivity. 

 

3.  ELECTRICAL CONNECTIONS 

3.1  SENSOR WIRING 

The TSH has 6 colored wires which are for sensor power and DPST relay output:  

Red - "+" DC Power 
Black - "-" DC Power 
White - Relay Common, Pole 1 
Green - Relay Normally Closed, Pole 1 
Blue - Relay Common, Pole 2 
Orange - Relay Normally Open, Pole 2 

The relay has 2 amp contacts and when the handle is touched, the relay energizes. Note that the 
contacts will also switch if the TSH loses power.  For additional safety, the 

operation of the TSH 

is fail safe

, itself.  When the TSH receives power, its control relay automatically energizes.  It 

deenergizes when the unit is touched.  For applications releasing an electric lock, Figure 3 shows 
typical connections of sensor, power supply and fail safe (locked when powered) electric locks.  
Fail secure electric locks are normally not used with the TSH on required exit applications.  N.O. 
contacts, however, are available from the sensor for special signaling applications and for 
integration with the Request to Exit (REX) function of an access control installation, as will be 
explained.  Note installation of the MOV in parallel with the electric lock.  The MOV is supplied 
loose with the TSH.  It is a black or blue disk-like component with two bare wires.  The MOV 
suppresses inductive kickback from the lock which shortens the life of the relay contacts if not 
suppressed.  It should be spliced in as close to the electric lock as possible.  It has no polarity.  

If, 

however, Securitron's Magnalock is used in the installation, the MOV is not necessary as 
the Magnalock is internally suppressed. 

FIG. 3:  TSH WIRING FOR FAIL SAFE ELECTRIC LOCK 

 

 

The sensor operates on 12-24 volts DC and is normally powered by the same power supply that 
operates the electric lock.  

When connecting power, polarity must be observed.

  Note that the 

sensor draws 

40 mA

 when "at rest" and 

25 mA

 when it is releasing the lock.  As an additional 

safety feature, 

the TSH includes a low voltage sensing circuit.

  The unit will keep working 

normally if input voltage declines until it reaches roughly 9 volts.  At that point, the TSH will 
automatically act as if all power was removed.  If a lock is being controlled, it will release.  Input 
voltage could decline if the unit was being operated on batteries and the batteries were 
discharging or because of a fault in the power supply. 

CABLE

RED (+ POWER)
BLACK (- POWER)
WHITE (RELAY COM1)
GREEN (RELAY N.C.1)

POWER SUPPLY

12-24 VDC

+

MOV

MAGNETIC

LOCK

NOTE 1: MOV NOT NEEDED IF SECURITRON MAGNALOCK USED

NOTE 2: POWER SUPPLY MUST ALWAYS CONNECT DIRECTLY TO SENSOR.

NOTE 3: POLARITY MUST BE OBSERVED WHEN CONNECTING POWER.

OTHER CONTROL SWITCHES SHOULD BREAK OR PARALLEL RELAY CONTACTS AS NEEDED.

Summary of Contents for TSH

Page 1: ...wood door By solid wood we mean a hardwood interior rather than pressed wood as the wood needs enough structural integrity to hold wood screws Note however that when the TSH is used on a solid door th...

Page 2: ...brown wire with a toothed ring terminal on its end soldered into the circuit board This is called the antenna wire It must make conductive contact with the aluminum handle to allow a person s touch t...

Page 3: ...OV in parallel with the electric lock The MOV is supplied loose with the TSH It is a black or blue disk like component with two bare wires The MOV suppresses inductive kickback from the lock which sho...

Page 4: ...Securitron products We provide such drawings in many of our manuals In this case the replacement of the generic products shown above with Securitron products is so simple as not to require separate dr...

Page 5: ...unit is on all of the time Slowly rotate the pot counter clockwise until you see the LED turn off and then another 15 degrees counter clockwise This is generally a good setting Then experiment by tou...

Page 6: ...is if a person could introduce a metal wire from the outside and make metal to metal contact with the handle The field could then propagate along the wire and be activated by the intruder s hand In p...

Page 7: ...oor Call the factory if you suspect noise induced problems Finally in very rare instances the sensor can hang up in a condition that continuously releases the door De power the unit and turn the adjus...

Page 8: ...Rev 8 00 Page 8...

Reviews: