CHALLENGE SOLUTION
Electronic noise interference
with Access Control System
CHECK for voltage from Magnalock to door
frame; there should be no voltage present.
DETERMINING WIRE GAUGE
The Magnalock requires adequate voltage and current for proper operation.
Resistance is created by the length and gauge (size) of the wire being used. An
accurate estimated distance from the power supply to the opening is crucial. For
superior operation the correct size gauge wire must be used—the devices used
operate optimally with the least amount of resistance on the source. Using the
correct gauge wires protects against large voltage and current (load) losses. The
gauge is determined by the wire distance, voltage and current of all devices.
1. CALCULATE total current for either a 12 VDC system (see Table 1, “12 VDC
System”) or a 24 VDC system (see Table 2, “24 VDC System), as required.
Table 1..12 VDC System Current Used
Devices Used
Amps (12 VDC)
Progressive
Totals
M62 Magnalock
0.250
0.250
DK-26 Access
0.160
0.410
XMS Motion
0.050
0.460
EEB2 Timer
0.025
0.485
Total Current (Rounded Up)
0.600A
Table 2. 24 VDC System
Devices Used
Amps (24 VDC)
Progressive
Totals
M82 Magnalock
0.200
0.200
TSB Touch Bar
0.025
0.225
DK-11 Access
0.070
0.295
XDT-24 Delay
0.050
0.345
MK Bypass/Reset
0.020
0.365
Total Current (Rounded Up)
0.400A