Installation
ASD 535, Mounting and installation, T 140 333 d en
35 / 40
3.6.4.2
Circuitry on selective identification or addressable loop via Al / St relay
•
For line technologies such as selective identification lines
and addressable loops, actuation of the auxiliary relay is to
be implemented from a software-controlled output (output
card or control module). The output is programmed via the
FACP software with the “Zone Off” and “Reset” functions.
•
If
Al I
and
Al II
are evaluated in the FACP as individual
zones (also 2-line dependency), programming of the SW
output is as follows:
Output switches when:
Zone A or B “Reset”
or:
Zone A and B “Off”
A normal relay or a PMR 81 semi-conductor relay can be used
as control relay.
Fig. 24 Wiring for selective identification or ad-
dressable loop
3.6.4.3
Circuitry on SecuriPro / SecuriFire / Integral addressable loop from XLM 35 / SLM 35
•
For the circuitry on SecuriPro / SecuriFire / Integral ad-
dressable loop from the XLM 35 / SLM 35 no additional
control relay is needed. Likewise, the
Al
and
St
relays of
the ASD 535 are not used. The state query and the control
of the ASD 535 take place directly between the XLM 35 or
SLM 35 and the addressable loop.
•
When using an ASD 535 with two smoke sensors and
XLM 35 / SLM 35 (ASD 535-2 or ASD 535-4), a 2-detector
dependency (
V-Al
/
H-Al
) can be programmed on the
FACP. Evaluation of the individual zones (
Al I
and
Al II
) in
the FACP is also possible.
•
On the
SLM 35
the S2 switch is positioned at “I” or “I + II”,
depending on the ASD type (number of smoke sensors).
Maximum connectable XLM 35 / SLM 35 units:
(see also notice box below)
per SecuriLine (only SLM 35)
50 units
per SecuriFire / Integral addressable loop
62 units
country-specific regulations and guidelines must be ob-
served
Fig. 25 Wiring from XLM 35 / SLM 35
Notices
•
There are two switches – S1 and S2 – on the
SLM 35
that have to be differently set depending on the use of
the ASD 535.
•
When operating an ASD 535-2 and ASD 535-4 (with 2 smoke sensors), two addresses are allocated on the
SLM 35
.
•
The circuitry and wiring routing between
SLM 35
and the FACP SecuriPro, SecuriFire or Integral must be car-
ried out as shown in
(X on X, Y on Y or X on L2, Y on C2, etc.).
•
The installation of the SecuriFire / Integral addressable loop must be shielded.
•
The circuitry and wiring routing between
XLM 35
and the FACP SecuriFire or Integral must be carried out as
•
The
identification sign
(EN 54-17) supplied with the XLM 35
must
be attached outside on the ASD (next to
the ASD rating plate).
_
_
_
_
Output switches when “Zone Off” and “Reset”
Inputs
Inputs
Alarm
transmitters
Alarm
transmitters
24
VDC
24
VDC
24
VDC
Line
Line
1
3
(L
O
A
D
)
4
2
Relay or
PMR 81
PMR 81 or
Relay
FACP
FACP
local
power supply
~/=
~/=
~/=
1)
1)
1)
2)
2)
from circuit-breaker card if not short-circuit proof
Reset
ASD 535-2 /-4
1 2 19 20
12
15
18
13
16
11
10
14
17
St
Al I
Al II
Reset
ASD 535-2 /-4
1 2 19 20
12
15
18
13
16
11
10
14
17
St
Al I
Al II
S
W
o
ut
pu
t
S
W
o
ut
pu
t
Local
power supply
2)
2)
1)
Protected
1)
2)
Screening, if required acc. to T 137 820E
Z/V U
Y X
T
D
at
a
D
at
a
G
N
D
G
N
D
_
24
VDC
14
C
13
MCU SecuriPro
SCB 01
MCB 02
S T U W X Y
D
at
a
D
at
a
G
N
D
G
N
D
Reset
ASD 535-1 to -4
AMB 35
SLM 35
1 2 19
10
20
18
St, Al I,
Al II
24
VDC
~/=
Local
power supply
VE
xt
5
G
nd
Ex
t5
X5
X2 /
1
Loop
SecuriFire / Integral
B5-DXI2
B5-PSU
G1
G2 L2
L1
C2
C1
Reset
ASD 535-1 to -4
AMB 35
1 2 19
10
20
18
St, Al I,
Al II
24
VDC
~/=
G
2
G
1
C
1
L1
L2
D
at
a
D
at
a
G
N
D
G
N
D
XLM 35
Summary of Contents for ASD 535
Page 4: ......