Installation
ASD 535, Mounting and installation, T 140 333 d en
29 / 40
3.5.1
Terminal assignment of AMB 35 Main Board
AMB terminal
Signal
Wiring
1
+10.5 to +30 VDC (UL/FM = 12.4 to 27)
Main supply line from FACP or external source
2
0 V
3
+10.5 to +30 VDC (UL/FM = 12.4 to 27)
Redundant supply line from FACP or external
4
0 V
5
+ Power supply
Wiring of
feedback loop signals
6
Output fault, OC (all fault events)
7
Output alarm I, OC
8
Output alarm II or freely programmable, OC
9
unused
10
Rel. 1 (“NO”)
Fault
Wiring the line
or specifications
of the used line
11
Rel. 1 (“NC”)
12
Rel. 1 “COM”
13
Rel. 2 “NO”
Alarm I
14
Rel. 2 “NC”
15
Rel. 2 “COM”
16
Rel. 3 “NO”
Alarm II
or freely programmable
17
Rel. 3 “NC”
18
Rel. 3 “COM”
19
Reset external input + (opto-isolator input)
Wiring
acc. to
and
20
Reset external input – (opto-isolator input)
21
+ F
+ power supply “F”
(may be available at a later date)
22
DF
Asynchronous data line “F”
23
-
0 V power supply “F”
24
+ S
+ power supply “S”
Connection MFU 535, REK 535
(available at a later date)
25
DS
Asynchronous data line “S”
26
-
0 V power supply “S”
Notice
The “Fault” relay has picked up in the normal state
contact Te. 12/10 closed, 12/11 open (ASD 535 under
voltage; no fault present).
AMB 35 internal connections
AMB terminal
Signal
Wiring
MOT / M-
Fan -
Fan, black wire
MOT / T
Fan tacho signal
Fan, white wire
MOT / M+
Fan +
Fan, red wire
OEM2 / Al-
Opto-isolator inputs for OEM2
Wiring
OEM2 / Al+
OEM2 / St-
OEM2 / St+
OEM1 / Al-
Opto-isolator inputs for OEM1
“
OEM1 / St
” can also be used for activating the
day/night control (priority over fault triggering).
OEM1 / Al+
OEM1 / St-
OEM1 / St+
Notices
•
In some cases, actuations may
not
comply with
EN 54-20
; thus, use only after consulting with the manufac-
turer).
•
The inputs are
not
line monitored.