Installation
30 / 40
ASD 535, Mounting and installation, T 140 333 d en
3.5.2
eXtended Line Module XLM 35 / SecuriLine module SLM 35 terminal assignment
SLM terminal
Signal
Wiring
L1 / T
Data A
Addressable loop
acc. to
or
C1 / U
GND A
G1 / V
Screen
L2 / X
Data B
Addressable loop
acc. to
or
C2 / Y
GND B
G2 / Z
Screen
3.5.3
Relay interface module RIM 35 terminal assignment
RIM terminal
Signal
Wiring
1
Rel. 1
“NO”
Pre-signal 1
or freely programmable
Local info or
wiring on FACP input
2
“NC”
3
“COM”
4
Rel. 2
“NO”
Pre-signal 2
or freely programmable
5
“NC”
6
“COM”
7
Rel. 3
“NO”
Pre-signal 3
or freely programmable
8
“NC”
9
“COM”
10
Rel. 4
“NO”
Dirty smoke sensor
or freely programmable
11
“NC”
12
“COM”
13
Rel. 5
“NO”
Sampling pipe pipe blockage
or freely programmable
14
“NC”
15
“COM”
Notice
Depending on the device version, the assigned criteria (signals) upon product delivery apply to smoke sen-
sor I on the first RIM 35 (connected to the AMB 35) and to smoke sensor II on the second RIM 35 (connected
to the first RIM 35, cascaded). The assignment of individual or all relays can be changed with the
“ASD Config” configuration software.
If two RIM 35 devices are deployed in the ASD 535-1 or -3, the relays of the second RIM 35 are not config-
ured with default criteria. The required programming must be performed with the “ASD Config” configuration
software.
3.5.4
Terminal assignment of an SIM 35 serial interface module
SIM terminal
Signal
Wiring / installation
1
GND
Input
1
st
conductor from wire pair 2
2
D +
1
st
conductor from wire pair 1
twisted
3
D –
2
nd
conductor from wire pair 1
4
GND
O
ut
put
1
st
conductor from wire pair 2
5
D +
1
st
conductor from wire pair 1
twisted
6
D –
2
nd
conductor from wire pair 1