SUPPORTED DEVICE AND COMMAND CLASSES
Z-Wave Device Classes
Generic Device Class
THERMOSTAT GENERIC DEVICE CLASS
Specific Device Class
THERMOSTAT GENERAL V2
Basic Device Class
ROUTING SLAVE
Implemented Device Classes
Z-Wave Command Classes
Manufacturer Specific
Secure Manufacture ID
Command Class
Version Command Class
Provides the version number of the Software
Multi Level Sensor
The SRT323 will respond to the Multilevel Sensor
Command Class
GET command with a Multilevel Sensor REPORT.
This report can be requested or sent unsolicited to
the nodes in Group 5. If the temperature sensor
functionality is disabled, the SRT323 will report 0x8000.
Basic Command Class
The Basic Command Class is mapped to the Setpoint
Command Class. The unit shall respond to the GET
command with a REPORT containing 0x00 if the
thermostat is not in comfort mode (5°C) or 0xFF if the
thermostat is in comfort mode (any other supported
temperature).
SET command ON (0x01 – 0x64 or 0xFF) sets the
setpoint to 21°C. SET command OFF (0x00) sets the
setpoint to 5°C. Any other value is ignored.”
Description
Continued on next page...