Because the machine internal relay is used for signal output, cannot directly drive large
power load, in order to ensure the long-term stable operation of the machine, the
electric lock be not connected directly with NO, NC, COM of the machine, but driven by
an access control special power supply.
When you enter the management mode or change the user PIN, you must press and
hold the * key for more than two seconds to be valid.
For the sake of safety, the default admin initial password 888888 only support the
menu 00, which force users to change the 6-digit admin password, or cannot access
other settings.
The factory default mode is the single-door mode. If you need other mode functions,
you must enter the appropriate mode to operate properly. In different modes, the
management menu is also different.
7 Common troubleshooting
Fault phenomenon
Possible causes
Troubleshooting
Indicator light is not
working properly
1. The power line is too thin
Replace thicker, qualified wire
2. Wrong connection or bad
contact of power line.
Wiring in the correct way.
Fail to enter
management mode.
1. Press the * key for more than 2
seconds before entering
password.
Operate in the right way.
2. Input wrong admin password.
Enter the correct password.
3. Forget admin password.
Change by Set-card or press the
# key to initialize.
Can enter
management mode,
but part of the menu
is invalid.
1. The machine mode is
incorrect, and some of the menus
are blocked.
Set to right machine mode.
User card can’t open
the door
1. It is not valid user card.
Add the user card again.
2. The user is disable.
Cancel the user disabling mode.
3. Incorrect door opening setting. Correct the door opening setting.
Reading card
1. Using the unqualified power
Change to linear power supply or