PrimeTest 300
Operating
Instructions
At the end of the test duration, the PrimeTest 300 will
compare the last reading with the Limit to determine the
outcome of the test. If the last reading is lower than the
Limit, a Pass result is recorded. This is indicated on the
display by a large tick mark next to the measurement
field, as shown below.
Similarly, if the last reading is greater than the Limit, a
Fail result is recorded. This is indicated by a large cross
next to the measurement field as shown below.
If the Earth Continuity test results in a Fail the sequence
is terminated.
The next test in the sequence for 230V Hand Held or
Portable Class I is an insulation resistance test. The
display is as shown below.
- 71 -