background image

TROUBLESHOOTING CHART

15

SYMPTOM

Motor will not run

Motor runs hot and
overload kicks off

Motor runs but no
water is delivered

*(Note: Check
prime before look-
ing for other
causes. Unscrew
pressure gauge
and see if there is
water in priming
hole)

Pump does not de-
liver water to full
capacity (Also
check point 3 im-
mediately above)

Pump pumps water
but does not shut
off

Pump cycles too
frequently

Air spurts from
faucets

POSSIBLE CAUSE(S)

1. Disconnect switch is off
2. Fuse is blown
3. Starting switch is defective
4. Wires at motor are loose, discon-

nected, or wired incorrectly

5. Pressure switch contacts are dirty
6. Wrong voltage

1. Motor is wired incorrectly
2. Voltage is too low

3. Pump cycles too frequently

*1. Pump in a new installation did not

pick up prime through:
a. Improper priming
b. Air leaks
c. Leaking foot valve

*2. Pump has lost its prime through:

a. Air leaks
b. Water level below suction of

pump

3. Ejector or impeller is plugged
4. Check valve or foot valve is stuck

in closed position

5. Pipes are frozen

6. Foot valve and/or strainer are

buried in sand or mud

1. Water level in well is lower than es-

timated

2. Steel piping (if used) is corroded or

limed, causing excess friction

3. Offset piping is too small in size

1. Pressure switch is out of adjust-

ment or contacts are “frozen”

2. Faucets have been left open
3. Ejector or impeller is clogged
4. Water level in well is lower than es-

timated

5. Wrong voltage

1. Standard pressure tank is water-

logged and has no air cushion

2. Pipes leak
3. Faucets or valves are open
4. Foot valve leaks
5. Pressure switch is out of adjust-

ment

6. Air charge too low in Captive Air

®

tank

1. Pump is picking up prime
2. Leak in suction side of pump
3. Well is gaseous
4. Intermittent overpumping of well

CORRECTIVE ACTION

1. Be sure switch is on
2. Replace fuse
3. Replace starting switch
4. Refer to instructions on wiring. Check and tighten all

wiring.

5. Clean by sliding piece of plain paper between contacts
6. Make sure motor voltage exactly matches power supply

voltage.

1. Refer to instructions on wiring
2. Check with power company. Install heavier wiring if wire

size is too small. See wiring instructions.

3. See section below on too frequent cycling

1. In new installation

a. Re-prime according to instructions
b. Check all connections on suction line, air volume con-

trol, and ejector

c. Replace foot valve

2. In installation already in use:

a. Check all connections on suction line, air volume con-

trol, ejector and shaft seal

b. Lower suction line into water and re-prime. If receding

water level in a shallow well operation exceeds suction
lift, a deep well pump is needed.

3. Clean ejector or impeller; see Maintenance
4. Replace check valve or foot valve

5. Thaw pipes. Bury pipes below frost line. Heat pit or pump

house.

6. Raise foot valve and/or strainer above well bottom

1. Lower ejector in well
2. Replace with plastic pipe where possible, otherwise with

new steel pipe

3. Use larger offset piping

1. Adjust or replace pressure switch

2. Close faucets
3. Clean ejector or impeller
4. Check possibility of using a deep well jet pump

5. Make sure motor voltage exactly matches power supply

voltage.

1. Drain tank to air volume control tapping. Check air volume

control for defects. Check for air leaks at any connection.

2. Check connections
3. Close faucets or valves
4. Replace foot valve
5. Adjust or replace pressure switch

6. Disconnect electrical power and open faucets until all

pressure is relieved. Using automobile tire pressure
gauge, check air pressure in tank at the valve stem lo-
cated at top of tank. If less than the pressure switch cut-in
setting, pump air into tank from outside source until the air
pressure is the same as cut-in setting of switch. Check air
valve for leaks, using soapy solution, and replace core if
necessary.

1. As soon as pump picks up prime, all air will be ejected
2. Check suction piping
3. Change installation, see Maintenance
4. Lower foot valve if possible, otherwise restrict discharge

side of pump

Summary of Contents for CRAFTSMAN 390.253251

Page 1: ...ing Instructions Before First Use of This Product Save This Manual For Future Reference Sears Roebuck and Co Hoffman Estates IL 60179 U S A Safety Instructions Installation Electrical Operation Mainte...

Page 2: ...or below at all times Over pressure can cause tank blowup in stall relief valve capable of passing full pump vol ume at 100 PSI 5 With a new well test well for purity before use Consult local Health...

Page 3: ...in the tank drops to 40 pounds per square inch PSI and stops the pump when the tank pressure reaches 60 PSI Adapter Flange The VMS pump is equipped with an adapter flange This adapter facilitates inst...

Page 4: ...3 2 2 1 1 HP 29902 60 11 0 9 5 8 6 7 8 6 6 5 4 4 7 4 6 4 2 3 4 2 6 1 7 40 11 7 11 1 10 2 9 2 7 8 6 4 5 1 5 0 4 5 4 0 3 2 2 1 29660 60 11 0 9 5 8 6 7 8 6 6 5 4 4 7 4 6 4 2 3 4 2 6 1 7 Multi Stage Pump...

Page 5: ...ough pump 8 Unions installed near pump and well will aid in ser vicing Leave room to use wrenches Motor normally operates at high temper ature and will be too hot to touch It is protected from heat da...

Page 6: ...always at least five feet from the bottom of the well 8 Tighten all hose clamps securely on plastic pipe Use two clamps per joint to prevent air leaks into suction pipe Clamp screws should be on oppos...

Page 7: ...e b Leather packer type ejector with built in foot valve c Turned couplings supplied with packer type ejector d Well casing adapter supplied with packer type ejector 1 Connect ejector to first length...

Page 8: ...mponents When water is drawn off through house fixtures the pressure in the tank is lowered and the pressure switch starts the pump Standard Tank Connection When a standard tank is used an air volume...

Page 9: ...ange voltage A B L2 L1 A B L2 L1 A B L2 L1 A B L2 L1 230 Volt to 115 Volt Conversion Spade Connector Type Move black wire from A to L1 1 1 2 2 3 3 3187 0398 A B L2 L1 A B L2 L1 Ground Screw Move white...

Page 10: ...igure 14 Page 9 Priming The Pump Burn hazard NEVER run pump dry Running pump without water may cause pump to overheat damaging seal and possibly causing burns to persons handling pump Fill pump with w...

Page 11: ...tem by alternately opening and closing faucets in the system With faucets open pressure will drop until pump starts with faucets closed pressure will build up until pump shuts off 7 There are conditio...

Page 12: ...cording the gauge you may have air leaks in the suction line or a clogged impeller Cleaning the Deep Well Jet 1 Disconnect power 2 Disconnect piping and well seal or casing adapter 3 Withdraw jet asse...

Page 13: ...screws holding the adapter bracket to the motor 15 With two screwdrivers on opposite sides of the pump carefully pry the pump adapter away from the motor This will pull the seal off of the motor shaf...

Page 14: ...the long cap screws to check this alignment It cannot be stressed too strongly that all bolt holes and water passages of all gaskets and volutes MUST line up with each other or the pump will not be as...

Page 15: ...iring 5 Clean by sliding piece of plain paper between contacts 6 Make sure motor voltage exactly matches power supply voltage 1 Refer to instructions on wiring 2 Check with power company Install heavi...

Page 16: ...TS 16 20 100 80 60 40 9 10 1 3 4 5 6 7 8 2 11 17 16 15 14A 14A 14B 14B 14C 13 14 18 1281 0994 12 12 2080 1095 1 1B 1A 2A 2B 2C 2D 5 4 6 2E 2F 2 3 7 8 9 10 20 100 80 60 40 Pressure Regulator Multi Stag...

Page 17: ...eq Key Part No Number Part Description 1 J112 14 Pressure Regulator Body w Seat 1A U111 212T Barbed Fitting Elbow 1B J66 16 Valve Seat 2 J220 16B Diaphragm Assembly 2A J42 5 Regulator Guide 2B J62 9 S...

Page 18: ...30 277ZP 3 8 16x2 1 2 Hex Hd Bolt 3 Req 7 J21 17 J21 21 Seal Ring Lower 8 J16 20ZZP J16 24ZZP Lower Flange 9 U36 38ZP U36 38ZP 3 8 Hex Nut 3 Req Key Part No Number Part Description 1 J20 12 Adapter Ga...

Page 19: ...rainer 12 U11 104P Plastic Pipe Adapter J216 13 J216 14 Casing Adapter U37 116GP U37 116GP 1 x 6 T O E Nipple Max Depth with Jet Package No 29670 29902 29660 Pump Venturi 2 Single 3 Single 4 Double Mo...

Page 20: ...or to inquire about an existing Agreement call 9 am 5 pm Monday Saturday 1 800 827 6655 M A I N T E N A N C E A G R E E M E N T America s Repair Specialists REPAIRSERVICES America s Repair Specialists...

Reviews: