background image

3

MAJOR COMPONENTS AND WHAT THEY DO

Tank and Air Volume Control

The tank serves two functions. It provides a reservoir
of water, so that the pump doesn’t need to start every
time water is drawn from a fixture in the house, and it
maintains a cushion of air under pressure.
When Captive Air

®

Tanks are used, no air volume con-

trol is necessary. This tank is precharged with air at the
factory.
When a Standard Tank is used, an air volume control
adds air to the tank when it is needed. See instructions
included with Air Volume Control for details on instal-
lation and operation.

Pressure Switch

The pressure switch provides automatic control.

Model No.

Pump Starts At

Pump Stops At

390.2505

30 Pounds

50 Pounds

When used with a Captive Air

®

Tank, the precharge

may need adjustment. See the Captive Air

®

Tank in-

structions for details.

Impeller and Jet

The impeller of the pump rotates with the motor shaft,
causing the water to fly out from its rim by centrifugal
force. The rotation of the impeller creates a partial vac-
uum which pulls in more water. Part of the water is di-
verted back to the jet where it passes through the
nozzle and venturi, reinforcing the vacuum to draw in
more water and delivering it at a high velocity to the
impeller.
Because of the shallow setting, the partial vacuum cre-
ated by the pump is sufficient to pull water to the
pump, therefore, the jet assembly is attached directly
to the pump.

Piping In The Well

A Shallow well jet pump can be installed on a dug well,
drilled well or with a driven point. SEARS shallow well jet
pumps have a built-in check valve. In a dug or cased well,
a foot valve and strainer is recommended and should be
installed 5 to 10 feet below the lowest level to which the
water will drop while pump is operating (pumping water
level), See Figure 3, Page 4. Your well driller can furnish
this information. The strainer should not be too close to
the bottom, or sediment may clog it. Before installing foot
valve, check to see that it works freely.
When using a foot valve, a priming tee and a plug as
shown in Figure 1, is recommended.
Be sure the total lift from the pumping water level to
the pump does not exceed 20 feet if the pump is over
the well, or less if the pump is offset from the well.
Both figures are for sea level – the maximum lift at
which the pump can operate satisfactorily decreases
with the elevation at the approximate rate of 1 foot per
1,000 feet of elevation. Thus, if the lift is 17 feet and

your elevation is 3,000 feet above sea level, you would
then be pumping 17 plus 3 or 20 feet. This is still sat-
isfactory for shallow well pumping.

Horizontal Piping From Well To Pump

On well point installations where the horizontal pip-
ing is more than 25 feet, a check valve should be in-
stalled as shown in Figure 3, Page 4.
When the pump is offset more than 25 feet from the
well, horizontal piping should be increased in size to
reduce friction losses. In no case should the offset pip-
ing be smaller than the suction tapping of the pump.

Horizontal Offset Piping Sizes
for Shallow Well Jets

1-1/4"

1-1/2"

2"

Up to 25 Ft.

25 to 50 Ft.

50 to 200 Ft.

Discharge Pipe Sizes

When the pump is set a distance from the house or
point of water use, the discharge pipe size should be
increased to reduce pressure losses caused by friction.

1"

1-1/4"

1-1/2"

Up to 25 Ft.

25 to 100 Ft.

100 to 600 Ft.

Emergency Power

In some areas and with some installations, an emer-
gency power supply to guard against power failure is a
good idea. If you install an engine-generator set for
emergency backup power for your pump, supply the
generator set manufacturer with the nameplate data
from the pump motor. He will then be able to provide
a generator of the correct size to power your pump.
Also, be sure to add the load from any other accessories
(such as lights) that may be on the same circuit.

Figure 1

Fill pump
and piping 
through 
Priming Tee

Relief
Valve

Summary of Contents for CRAFTSMAN 390.2505

Page 1: ...perating Instructions Before First Use of This Product Save This Manual For Future Reference Sears Roebuck and Co Hoffman Estates IL 60179 U S A Safety Instructions Installation Electrical Maintenance...

Page 2: ...rent supply agree with the motor wiring as shown on motor nameplate 10 The correct fusing and wiring sizing is essential to proper motor operation Use recommended fusing and wire size data in the manu...

Page 3: ...mation The strainer should not be too close to the bottom or sediment may clog it Before installing foot valve check to see that it works freely When using a foot valve a priming tee and a plug as sho...

Page 4: ...d possibly causing burns to persons handling pump Fill pump with water before starting Never run pump against closed dis charge To do so can boil water inside pump causing hazardous pressure in unit r...

Page 5: ...ike the one at right Dial Type Voltage Selector To change to 115 volts 1 Make sure power is off 2 Turn the dial counter clockwise until 115 shows in the dial window 3 Reinstall the Motor end cover 4 G...

Page 6: ...large as the power supply wires 3 Connect the ground wire to a grounded lead in a ser vice panel to a metal underground water pipe to a metal well casing at least ten feet 3M long or to a ground elect...

Page 7: ...w be removed 3 Carefully tap diffuser to remove from seal plate 4 Remove canopy from end of motor 5 Partially unscrew capacitor clamp move capacitor to one side 6 Hold motor shaft with 7 16 wrench on...

Page 8: ...ameter pointed tool into the nozzle and dislodge foreign material If it is not possible to push the obstruction through the nozzle or if the nozzle is damaged follow in structions above under Replacin...

Page 9: ...m buried in sand or mud Pump does not 1 Water level in well is lower than 1 A deep well jet pump may be needed over 20 ft to water deliver water to full estimated capacity Also 2 Steel piping if used...

Page 10: ...zzle No 43 11 U111 211T 1 Hose Barb 12 2 Pipe Plug 1 4 NPT Hex Head 13 N212 12P 1 Check Valve 14 1 Pipe Plug 1 8 NPT Square Head 15 N176 38A 1 Pump Body Assembly 16 4 Capscrew 3 8 16x1 1 4 Hex Head 17...

Page 11: ...6 U37 17GPT Nipple 1 4 x 1 1 2 37 U37 205P Tube AVC 38 U111 86T Compression Fitting Elbow 1 4 NPT 39 U111 100T Compression Fitting Straight 1 8 NPT Standard hardware item May be purchased locally Shal...

Page 12: ...r replacement parts you need Call 7 am 7 pm 7 days a week 1 800 366 PART 1 800 366 7278 For in home major brand repair service Call 24 hours a day 7 days a week 1 800 4 REPAIR 1 800 473 7247 For the l...

Reviews: