background image

5.  OPERATION

 

‰

  

WARNING!

 Ensure that you have read, and fully understood and apply Section 1 Safety Instructions.

5.1.    

IMPORTANT

. The use of extension leads to connect this compressor to the mains is not recommended as the resulting voltage    

 

drop reduces motor, and therefore pump performance and could damage your compressor.

5.2. 

  

Confirm that the mains voltage corresponds with the voltage shown on the compressor data plate.

5.3. 

  

The compressor should be operated on a horizontal flat surface, or one that does not exceed 5° either transversely (tyres fully inflated  

 

to 1.5bar) or longitudinally with chocks (fig 2), and should be in a position that allows good air circulation around the unit, 1000mm    

 

nominal gap.

5.4. 

  

Before using the compressor check the oil level by referring to the oil sight glass (fig 3). On a horizontal surface, if the oil level is not   

 

up to the red centre mark it should be further topped up with recommended oil, see section 6.7.

5.5. 

  

To top up undo filler cap (fig 3), top up oil level to required level, then replace filler cap.

5.6. 

  

Take care when selecting tools for use with the compressor. Air tool manufacturers normally express the volume of air to operate   

 

a tool in cubic feet per minute (cfm). This refers to free air delivered by the compressor (‘air out’) which varies according to the        

 

pressure setting. 

DO NOT

 confuse this with the compressor displacement which is the air taken in by the compressor (‘air in’).       

 

‘Air out’ is always less than ‘air in’ due to losses within the compressor. 

5.7. 

  

STARTING THE COMPRESSOR.

5.7.1. 

  

Your compressor is fitted with a push/pull type ON/OFF button to turn the compressor “ON” pull the ON/OFF button upwards.

 

To turn the compressor “OFF” push the ON/OFF button downwards (fig 3).

5.7.2. 

  

Check that the ON/OFF button is in the “OFF” position and the regulator dial 

(fig 5) is closed (Zero ‘0’ bar).

5.7.3. 

  

Plug mains lead into mains supply and start the compressor pulling the ON/OFF button (fig 3) upwards.

5.7.4. 

  

Leave the compressor running with no air line or tools connected, and regulated pressure gauge (fig 5) set to maximum pressure     

 

(fully clockwise). Make sure that the pressure in the tank rises and that the compressor stops automatically when the maximum is    

 

reached. This value is written on the specification plate and shown on the direct pressure gauge (fig 5). This may take in excess of 5  

 

minutes. The compressor will now operate automatically. 

 

The pressure switch (fig 6) stops the motor when the maximum tank pressure is reached and restarts it when pressure falls below the  

 

minimum threshold approximately 2bar (29psi) less than the  maximum pressure.

5.7.5. 

  

Stop the compressor by pushing the ON/OFF button 

(fig 3) 

downwards. The compressed air inside the compressor head will flow out   

 

via the air line tube situated beneath the switch housing. Restart is made easier and prevents the motor from being damaged.  

 

 

DO NOT

, other than in an emergency, stop the compressor by switching off the mains power, or by pulling the plug out, as the 

 

 

pressure relief will not then occur and motor damage may result upon restart.

 

When the compressor runs correctly and is stopped correctly there will be: 

 

A:

 A whistle of compressed air when the motor stops,

 

B:

 A protracted whistle (about 20-25 seconds) when the compressor starts with no pressure in the tank.

5.7.6. 

  

The output pressure is regulated by the pressure regulator (fig 5). Turn the pressure regulator dial clockwise to increase pressure and  

 

counter-clockwise to reduce it.

 

  To determine the correct working pressure for any piece of equipment check the corresponding manual. 

 

 

 

 

  When the compressor is not being used set the regulated pressure to zero so as to avoid damaging the pressure reducer.

 

NOTE:

 

A:

 If the motor does not cut in and out, but runs continuously when using an air appliance, the capacity of the compressor may    

 

be too small for the equipment or tool.

Original Language Version

© Jack Sealey Limited

   fig.3

   fig.5

   fig.4

   fig.6

   fig.2

SAC3103B  Issue 4 (3,4,5) 01/04/22

Summary of Contents for SAC3103B

Page 1: ...t the BLUE neutral wire to the neutral terminal N d After wiring check that there are no bare wires that all wires have been correctly connected that the cable restraint is tight 1 1 1 SAC3203B is supplied with a flying lead without a plug Jack Sealey Limited recommend a 16 amp protected supply When connecting to a 16 amp protected supply contact a qualified electrician to ensure connection to a s...

Page 2: ...ckness at any point WARNING If an electrical fuse blows ensure it is replaced with an identical fuse type and rating 9 When not in use store the compressor carefully in a safe dry childproof location 9 When the compressor is not in use it should be switched off disconnected from the mains supply and the air drained from the tank 1 3 INSPECTION OF PRESSURE TANK BOTH INTERNAL AND EXTERNAL 1 3 1 Unde...

Page 3: ... start the compressor pulling the ON OFF button fig 3 upwards 5 7 4 Leave the compressor running with no air line or tools connected and regulated pressure gauge fig 5 set to maximum pressure fully clockwise Make sure that the pressure in the tank rises and that the compressor stops automatically when the maximum is reached This value is written on the specification plate and shown on the direct p...

Page 4: ...Replace filler cap B Check the automatic cut out at maximum pressure and the automatic cut in at 2bar below WARNING Never mix different oils and DO NOT use non detergent low quality oils as the compressor may be damaged WARNING Dispose of waste oil only in accordance with local authority requirements 6 6 OPERATIONS TO BE CARRIED OUT EVERY 500 HOURS A Replace air filter figs 1 4 B Check all tube fi...

Page 5: ...ste authority for recycling information Note It is our policy to continually improve products and as such we reserve the right to alter data specifications and component parts without prior notice Important No Liability is accepted for incorrect use of this product Warranty Guarantee is 24 months from purchase date proof of which is required for any claim 4B Motor stops and will not restart Supply...

Reviews: