©Sealevel Systems, Inc.
HazPAC R9-8.4 Manual
13
SL9257 8/2015
OPEN COLLECTOR OUTPUTS
Directly control eight outputs via the HazPAC R9-8.4’s open-collector outputs found on the
front of the enclosure. The open collector outputs have a range of 5 – 30V with a maximum
sink current of 500mA on a single output with a combined maximum sink current of 580mA on
all outputs.
Connector:
OPEN-COLLECTOR OUTPUTS
Manufacturer:
Weco
Part Number:
110-M-111/10
Description:
Terminal Block 10 position 3.5mm spacing
Mates with:
Weco 110-A-111/10 10 position screw-terminal plug (provided)
Pin
Signal
0V
GND
1
Output 1
2
Output 2
3
Output 3
4
Output 4
5
Output 5
6
Output 6
7
Output 7
8
Output 8
Vin
OCVCC