In cool mode, if the unit displays “E4”, this indicates that the indoor coil is not less than the
room temperature – 5.4
º
F for over 5 minutes. Unit will enter protect mode and shut down.
When unit is started in heat mode, if the compressor runs for more than 20 minutes and the coil
temperature has not reached sufficient temperature, the Unit will enter protect mode, display
“E4”, and shutdown.
When operating in heat mode, If the compressor runs continuous for more than 35 minutes,
and the indoor fan hasn’t started, the unit will enter protect mode, display “E4”, and shut
down.
After the compressor continuous running over twenty minutes and inside blower fan
continuous stop running or compressor continuous running and inside blower fan stop
continuous 35 minutes at first turn on in heating mode, system display E4 and shut down.
1.10 Error codes
This unit has advanced diagnostics and monitoring, and can provide information to the user in
the event of a problem with the operation of the system. The codes produced are explained
below.
E4 in the Cooling mode indicates low refrigerant.
failure
display
Communication failure of wall
thermostat
E1
Inside room temp. sensor failure
E2
Inside coil temp. sensor failure
E3
Unit abnormal
E4
Outside coil temp. sensor failure
E5
Frost or over heat protection
E8
defrost
DF
Summary of Contents for PTAC09CH3ZX
Page 8: ...953 0002 revC 07 06 09 PAGE 8 2 0 Schematic diagrams PTACC9CH3ZX ...
Page 9: ...953 0002 revC 07 06 09 PAGE 9 PTAC09HP3ZX ...
Page 10: ...953 0002 revC 07 06 09 PAGE 10 PTAC12CH3ZX ...
Page 11: ...953 0002 revC 07 06 09 PAGE 11 PTAC12CH5ZX ...
Page 12: ...953 0002 revC 07 06 09 PAGE 12 PTACHP3ZX ...
Page 13: ...953 0002 revC 07 06 09 PAGE 13 PTAC15CH3ZX ...