1. Function of the Control Board (PC board) 

1.1 Cooling 

 

The indoor temperature is monitored by the room temperature sensor. The temperature is 

controlled by the cyclic switch of the compressor under which is controlled by the Control 
Board. 

 

Compressor startup is determined when the room temperature is more than or equal to 

Ts+3.6

 (Ts is the setpoint  temperature). When this occurs, the compressor, condenser fan, 

and inside blower fan starts. 

 

When the setpoint is satisfied as determined by the temperature sensor, the compressor, 

condenser fan, and the blower fan will stop. This cycle will start again when the 
temperature rises as notes before. 

 

a.  Working curve for temperature control 

 

1.2 Freeze protection and frost protection function of unit 

 

When the outdoor coil temperature is less than or equal to 57 ºF, the compressor will not 

run. The blower will continue to run at its set speed. 

 

After the compressor runs continuous for over 3 minutes and if coil pipe temperature of 

inside is continuously ≤ 5ºF for over 3 minutes, then the compressor will shut off. The blower 
fan will continue to run. The system will restart after 6 minutes. If the system goes into this 
condition again, the unit will shut down and display error code of E8.(See Error Code 
Chart) 

 

1.3Heating  

 

The indoor temperature is monitored by the room temperature sensor. The temperature is 

controlled by the cyclic switch of the compressor under which is controlled by the Control 
Board. 

 

Normally, in heating mode, the compressor and the outside blower fan will start. The Four-

Summary of Contents for PTAC09CH3ZX

Page 1: ...MODEL HEAT COOL BTU ELECTRIC HEAT WATTS PTAC09CH3ZX 9 600 3 000 PTAC12CH3ZX 12 000 3 000 PTAC12CH5ZX 12 000 5 000 PTAC15CH3ZX 15 000 3 000 PTAC15CH5ZX 15 000 5 000 MODEL HEAT COOL BTU ELECTRIC HEAT WATTS PTAC09CH3ZX 9 000 3 000 PTAC12CH3ZX 12 000 3 000 PTAC12CH5ZX 12 000 5 000 PTAC15CH3ZX 15 000 3 000 PTAC15CH5ZX 15 000 5 000 ...

Page 2: ...curve for temperature control 1 2 Freeze protection and frost protection function of unit When the outdoor coil temperature is less than or equal to 57 ºF the compressor will not run The blower will continue to run at its set speed After the compressor runs continuous for over 3 minutes and if coil pipe temperature of inside is continuously 5ºF for over 3 minutes then the compressor will shut off ...

Page 3: ...an stops and the four way valve will close The compressor will stop for 2 minutes before restarting defrost process In the heating mode the Blower fan will run at the set speed while the electric heater is operating when the electric heater stops The blower fan will shut down after running on low speed for 15 seconds ...

Page 4: ...eaters When the room temperature is less than Ts 3 6ºF Ts is the setpoint temperature the compressor and outdoor fan will run When the room temperature is more than or equal to the set temperature Ts the compressor and outdoor fan will shut down In order for the electric heat to operate the following conditions must be met The compressor outdoor fan and the indoor blower fan must be operating The ...

Page 5: ...133ºF the outside blower fan shuts down and the system will enter overload protection When the coil temperature of the inside unit is 125 6ºF normal operation will resume 1 5 Defrosting The system will enter defrost under the following conditions The compressor has been running in heat mode for over 7 minutes The outside coil temperature 9ºF Defrost time is determined by the operating time of the ...

Page 6: ... changed Timer function will not operate in Automatic mode Heat Pump Models Room temperature Ts 79 79 TR 70 TR 70 Mode cool Fan Only Heating Cooling only model Room temperature Ts 79 79 TR State cooling Ventilation 1 8 Start and Stop Timer functions If the unit is ON pressing the timer button will create a shutdown time The display will show 1 to 12 hours I E 2H Pressing the hour button will incre...

Page 7: ...mode display E4 and shut down After the compressor continuous running over twenty minutes and inside blower fan continuous stop running or compressor continuous running and inside blower fan stop continuous 35 minutes at first turn on in heating mode system display E4 and shut down 1 10 Error codes This unit has advanced diagnostics and monitoring and can provide information to the user in the eve...

Page 8: ...953 0002 revC 07 06 09 PAGE 8 2 0 Schematic diagrams PTACC9CH3ZX ...

Page 9: ...953 0002 revC 07 06 09 PAGE 9 PTAC09HP3ZX ...

Page 10: ...953 0002 revC 07 06 09 PAGE 10 PTAC12CH3ZX ...

Page 11: ...953 0002 revC 07 06 09 PAGE 11 PTAC12CH5ZX ...

Page 12: ...953 0002 revC 07 06 09 PAGE 12 PTACHP3ZX ...

Page 13: ...953 0002 revC 07 06 09 PAGE 13 PTAC15CH3ZX ...

Page 14: ...953 0002 revC 07 06 09 PAGE 14 PTAC15CH5ZX ...

Page 15: ... PAGE 15 PTAC15HZ3ZX IF YOU NEED TECHNICAL SUPPORT PLEASE CALL 704 504 8590 BETWEEN THE HOURS OF 8 00 A M AND 5 00 P M PLEASE HAVE YOUR EQUIPMENT MODEL NUMBER ANDSERIAL NUMBER AVAILABLE WHEN YOU CALL http www irproducts biz ...

Reviews: