1. Function of the Control Board (PC board)
1.1 Cooling
●
The indoor temperature is monitored by the room temperature sensor. The temperature is
controlled by the cyclic switch of the compressor under which is controlled by the Control
Board.
●
Compressor startup is determined when the room temperature is more than or equal to
Ts+3.6
℉
(Ts is the setpoint temperature). When this occurs, the compressor, condenser fan,
and inside blower fan starts.
●
When the setpoint is satisfied as determined by the temperature sensor, the compressor,
condenser fan, and the blower fan will stop. This cycle will start again when the
temperature rises as notes before.
a. Working curve for temperature control
1.2 Freeze protection and frost protection function of unit
●
When the outdoor coil temperature is less than or equal to 57 ºF, the compressor will not
run. The blower will continue to run at its set speed.
●
After the compressor runs continuous for over 3 minutes and if coil pipe temperature of
inside is continuously ≤ 5ºF for over 3 minutes, then the compressor will shut off. The blower
fan will continue to run. The system will restart after 6 minutes. If the system goes into this
condition again, the unit will shut down and display error code of E8.(See Error Code
Chart)
1.3Heating
●
The indoor temperature is monitored by the room temperature sensor. The temperature is
controlled by the cyclic switch of the compressor under which is controlled by the Control
Board.
●
Normally, in heating mode, the compressor and the outside blower fan will start. The Four-
Summary of Contents for PTAC09CH3ZX
Page 8: ...953 0002 revC 07 06 09 PAGE 8 2 0 Schematic diagrams PTACC9CH3ZX ...
Page 9: ...953 0002 revC 07 06 09 PAGE 9 PTAC09HP3ZX ...
Page 10: ...953 0002 revC 07 06 09 PAGE 10 PTAC12CH3ZX ...
Page 11: ...953 0002 revC 07 06 09 PAGE 11 PTAC12CH5ZX ...
Page 12: ...953 0002 revC 07 06 09 PAGE 12 PTACHP3ZX ...
Page 13: ...953 0002 revC 07 06 09 PAGE 13 PTAC15CH3ZX ...