whatever the chosen configuration.
CONSEQUENCES
Unreliability of the equipment.
Immediately control the system and the
transformer
RESOLUTION
In order to acknowledge the FAULT signal, press at
the same time for 5 seconds the keys
AUTO/MANUAL/SCAN and ARROW UP. (In the
panel, the two keys are connected by the graphic
RESET sign)
Check:
- the arrangement of the probe cables
- the presence of inverters
- that the connections to the junction boxes are
adequate
ALARM
DESCRIPTION
This is the alarm signal which indicates when a
critical status is reached for the functioning of the
controlled equipment.
ACTIONS
- The ALARM relay energizes
- The related ALARM led switches on
INTERVENTION
- Exceeding the alarm temperature "A". The value
of the measured temperature is higher than the
temperature set for the alarm.
- Breakdown or anomaly to the thermometer
probes (see table no. 1 "relay interventions")
CONSEQUENCES
Immediately control the probes and the
transformer