REG
TYPE
DATA
RANGE
1
READ ONLY
Temperature channel 1
-1000/+20000
2
READ ONLY
Temperature channel 2
-1000/+20000
3
READ ONLY
Temperature channel 3
-1000/+20000
4
READ ONLY
Temperature channel 4
-1000/+20000
5
READ ONLY
Historical max temp. Ch 1
-1000/+20000
6
READ ONLY
Historical max temp. Ch.2
-1000/+20000
7
READ ONLY
Historical max temp. Ch 3
-1000/+20000
8
READ ONLY
Historical max temp. Ch 4
-1000/+20000
9
READ ONLY
Channel fault
0 / 0x000F
10
READ ONLY
Relays status
0 / 0x000F
20
READ WRITE
Function mode
0/3
21
READ WRITE
Channel enable
0 / 0x000F
22
READ WRITE
Fan status
0 / 0x000F
23
READ WRITE
Allarm channel 1
-1000/+20000
24
READ WRITE
Allarm channel 2
-1000/+20000
25
READ WRITE
Allarm channel 3
-1000/+20000
26
READ WRITE
Allarm channel 4
-1000/+20000
27
READ WRITE
Trip channel 1
-1000/+20000
28
READ WRITE
Trip channel 2
-1000/+20000
29
READ WRITE
Trip channel 3
-1000/+20000
30
READ WRITE
Trip channel 4
-1000/+20000
31
READ WRITE
Fan low level channel 1
-1000/+20000
32
READ WRITE
Fan low level channel 2
-1000/+20000
33
READ WRITE
Fan low level channel 3
-1000/+20000
34
READ WRITE
Fan low level channel 4
-1000/+20000
35
READ WRITE
Fan hight level channel 1
-1000/+20000
36
READ WRITE
Fan hight level channel 2
-1000/+20000
37
READ WRITE
Fan hight level channel 1
-1000/+20000
38
READ WRITE
Fan hight level channel 2
-1000/+20000