SPECIFICATION TABLE
SEA-FIRE “FD” SERIES AUTOMATIC FIRE EXTINGUISHERS
4B/360, 4BW/500 CYLINDERS
AREA OF
MINIMUM
MAXIMUM
DIAMETER X
FD MODEL
PROTECTION
FM-200
®
FM-200
®
HEIGHT
MAN/
CU.FT.
CU.M.
AUTO
AUTO
RANGE
RANGE
LBS
KG
LBS
KG
IN
MM
FD150A
FD150M
126-150
3.5-4.2
5.4
2.4
6.5
2.9
5.1x17
130x432
FD175A
FD175M
151-175
4.2-5.0
6.5
2.9
7.6
3.4
5.1x17
130x432
FD200A
FD200M
176-200
5.0-5.7
7.6
3.4
8.7
3.9
5.1x17
130x432
FD225A
FD225M
201-225
5.7-6.4
8.7
3.9
9.7
4.4
6.1x17
160x432
FD250A
FD250M
226-250
6.4-7.1
9.7
4.4
10.8
4.9
6.1x17
160x432
FD275A
FD275M
251-275
7.1-7.8
10.8
4.9
11.9
5.4
6.1x17
160x432
FD300A
FD300M
276-300
7.8-8.5
11.9
54
13.0
5.9
6.1x17
160x432
FD325A
FD325M
301-325
8,2-9.2
13.0
5.9
14.0
6.4
6.1x17
160x432
FD350A
FD350M
326-350
9.2-9.9
14.0
6.4
15.2
6.9
6.1x17
160x432
FD400A
FD400M
351-400
9.9-11.3
15.2
6.9
17.3
7.8
7.1x18
180x457
FD450A
FD450M
401-450
11.3-12.7
17.3
7.8
19.5
8.8
7.1x18
180x457
FD500A
FD500M
451-500
12.7-14.2
19.5
8.8
21.7
9.8
7.1x18
180x457
FD550A
FD550M
501-550
14.2-15.6
21.7
9.8
23.8
10.8
7.1x18
180x457
FD600A
FD600M
551-600
15.6-17.0
23.8
10.8
26.0
11.8
8.1x22
206x559
FD650A
FD650M
601-650
17.0-18.4
26.0
11.8
28.1
12.7
8.1x22
206x559
FD700A
FD700M
651-700
18.4-19.8
28.1
12.7
30.3
13.7
8.1x22
206x559
FD750A
FD750M
701-750
19.8-21.2
30.3
13.7
32.5
14.7
8.1x22
206x559
FD800A
FD800M
751-800
21.2-22.7
32.5
14.7
34.6
15.7
8.1x33
206x838
FD850A
FD850M
801-850
22.7-24.1
34.6
15.7
36.8
16.7
8.1x33
206x838
FD900A
FD900M
851-900
24.1-25.5
36.8
16.7
39.0
17.7
8.1x33
206x838
FD950A
FD950M
901-950
25.5-26.9
39.0
17.7
41.1
18.6
8.1x33
206x838
FD1000A
FD1000M
950-1000
26.9-28.3
41.1
18.6
43.3
19.6
8.1x33
206x838
FD1050M
1001-1050
28.3-29.8
43.3
19.6
45.5
20.5
10x26
254x660
FD1100M
1051-1100
29.8-31.1
45.5
20.5
47.6
21.6
10x26
254x660
FD1150M
1101-1150
31.1-32.6
47.6
21.6
49.8
22.6
10x26
254x660
FD1200M
1151-1200
32.6-34.0
49.8
22.6
52.0
23.6
10x26
254x660
FD1250M
1201-1250
34.0-35.4
52.0
23.6
54.1
24.5
10x26
254x660
FD1300M
1251-1300
35.4-36.8
54.1
24.5
56.3
25.5
10x26
254x660
FD1350M
1301-1350
36.8-38.2
56.3
25.5
58.5
26.5
10x26
254x660
FD1400M
1351-1400
38.2-39.6
58.5
26.5
60.6
27.5
10x26
254x660
FD1450M
1401-1450
39.6-41.1
60.6
27.5
62.8
28.5
10x26
254x660
FD1500M
1451-1500
41.1-42.5
62.8
28.5
65.0
29.5
10x26
254x660
OPERATING TEMPERATURE RANGE:
20° TO 130°F (-7° TO 54°C) FD MODELS
DISCHARGE TEMPERATURE:
FD-150 thru FD-1500 175°F (79°C)
MODEL FD-150 thru FD-1000 APPROVED FOR VERTICAL OR HORIZONTAL MOUNTING
MODEL FD-1050 thru FD-1500 FOR VERTICAL MOUNTING ONLY
Cubic Feet = CU.FT.
Kilograms = KG
Cubic Meters = CU.M.
Inches = IN
Pounds = LBS
Millimeters = MM
V M
E O
R U O
T N N
I T L
C I Y
A N
L G
14
Step 5
Locate bracket in desired position (Vertical-Sensor Valve/Detector Head Up, or
Horizontal, Figure 2). Using the bracket as a template, mark and drill holes in bulkhead
and install bracket insuring that all bolts are thoroughly tight.
Figure 2
WARNING: When installing cylinder in horizontal position, the actuator (top of cylinder)
must NEVER be lower than the bottom of the cylinder or proper discharge of agent will not
occur (see Figure 2 above).
MODELS FD1100 THRU FD1500 MUST BE INSTALLED VERTICAL ONLY
Step 6 Carefully attach cylinder to bracket. Sensor valve/Detector head should point towards
engine or center of the compartment. Nameplate should be visible. Tighten bracket
straps so that the cylinder body is firmly and securely held in place by its’ bracket.
CABLE ASSEMBLY INSTALLATION
(for FG and FD systems with “M” designation - manual discharge capability:
Model SMAC-XX is required.)
CAUTION: TO PREVENT ACCIDENTAL DISCHARGE DURING CABLE INSTALLATION,
VERIFY THAT THE MANUAL DISCHARGE LEVER SAFETY PIN IS PROPERLY INSTALLED
(SEE FIGURE 6A OR 7C).
Step 1
Select the proper location.
a. Manual discharge release handles should never be installed in the protected
compartment.
b. Locate discharge handle at the helm station with full view and easy access by the
operator.
c. The area selected must be structurally secure and provide at least twelve (12)
inches (305mm) of clearance at the rear of the panel to facilitate cable hardware.
d. Do not install actuator cable in area where the possibility of physical abuse is likely.
Where practical, follow the same cable path as installed by boat manufacturer.
e. The cumulative number of bends in the cable run must never exceed 360 degrees.
This is equivalent to four (4) right (90°) angles. Use extreme care when bending
cable to avoid kinking. Never form a bend with a radius of less than twelve (12)
inches (305mm). Selection of the correct size Sea-Fire cable length will eliminate
cable coil.
Step 2 Mounting manual cable, faceplate, and release handle.
a. Using the manual discharge faceplate as a template (Figure 5) mark and drill a
13/32 inch (10.4mm) hole. Install the manual release cable adhering to the
guideline in Step 1 above.
b. Do not connect cable to the cylinder at this time.
c. Remove the protective backing from the faceplate. While aligning the holes, place
even pressure upon the faceplate. To insure a good bond, the temperature should
be in excess of 50°F (10°C).
7