FM200

®

MODEL FG & FD FIRE EXTINGUISHERS

INSTALLATION INSTRUCTIONS

OWNER’S MANUAL

THIS MANUAL IS AN INTEGRAL PART OF THE SYSTEM AND AS SUCH, THE

EXTINGUISHER MUST BE INSTALLED AND MAINTAINED ACCORDINGLY.

U.S. COAST GUARD APPROVED   FM APPROVED

No. 162.029/237/0

READ AND COMPLY WITH THESE INSTRUCTIONS, WARNINGS

AND LIMITATIONS BEFORE INSTALLING.

SUITABLE FOR USE FG MODELS: 0°F (-18°C) TO 130°F (54°C)

FD MODELS: 20°F (-7°C) TO 130°F (54°C).

ALWAYS MAINTAIN THIS OWNER’S MANUAL NEARBY

FOR OPERATOR REFERENCE.

OWNERS MANUAL PN: 123-194, REV. B

PRINTED IN USA

1

Summary of Contents for FD1000A

Page 1: ...FIRE EXTINGUISHERS INSTALLATION INSTRUCTIONS OWNER S MANUAL THIS MANUAL IS AN INTEGRAL PART OF THE SYSTEM AND AS SUCH THE EXTINGUISHER MUST BE INSTALLED AND MAINTAINED ACCORDINGLY U S COAST GUARD APPROVED FM APPROVED No 162 029 237 0 READ AND COMPLY WITH THESE INSTRUCTIONS WARNINGS AND LIMITATIONS BEFORE INSTALLING SUITABLE FOR USE FG MODELS 0 F 18 C TO 130 F 54 C FD MODELS 20 F 7 C TO 130 F 54 C ...

Page 2: ... DISCLAIMER OF EXPRESSED AND IMPLIED WARRANTIES Metalcraft Sea Fire Marine Inc has taken reasonable care in preparing this document how ever since the use of this information and the conditions of use of the product are not within the control of Metalcraft Sea Fire Marine Inc it is the user s obligation to determine the con ditions of safe use of this product The information in this document is of...

Page 3: ...nd or heart irregularities arrhythmias Misuse of the products by deliberately inhaling high concentrations of this gas could cause death without warning Persons with preexisting cardiac or central nervous sys tem disorders may be more susceptible to effects of an overexposure Section 12 Ecological Information No ecological information is available Section 13 Disposal Considerations Dispose of wast...

Page 4: ...t the combustion reaction cannot sustain itself CAUTION IN CASE OF EXTINGUISHER DISCHARGE DO NOT RUSH TO OPEN THE PROTECTED COMPARTMENT LET THE EXTINGUISHING AGENT WORK FOR SEVERAL MINUTES HAVE A PORTABLE EXTINGUISHER AVAILABLEAND USE CARE WHEN OPENING THE COMPARTMENT AVOID BREATHING FIRE RELATED FUMES OR VAPOR NOTE It is important to retain the designed vapor concentration within the compartment ...

Page 5: ... 2 0 AMPS AT 28 VDC For applications requiring larger load capacities see optional equipment section in this manual or contact factory ENGINES AND POWERED VENTILATION BLOWERS DIESEL ENGINES Continued operation of diesel engine s and or powered ventilation units will deplete the extinguishing agent and may cause a fire re flash Diesel engine s must be automatically shutdown upon extinguisher discha...

Page 6: ...26 150 3 5 4 2 5 4 2 4 6 5 2 9 5 2x17 0 132x476 FD175A FD175M 151 175 4 2 5 0 6 5 2 9 7 6 3 4 5 2x17 0 132x476 FD200A FD200M 176 200 5 0 5 7 7 6 3 4 8 7 3 9 5 2x17 0 132x476 FD225A FD225M 201 225 5 7 6 4 8 7 3 9 9 7 4 4 5 2x17 0 132x476 FD250A FD250M 226 250 6 4 7 1 9 7 4 4 10 8 4 9 6 9x18 0 175x463 FD275A FD275M 251 275 7 1 7 8 10 8 4 9 11 9 5 4 6 9x18 0 175x463 FD300A FD300M 276 300 7 8 8 5 11 9...

Page 7: ...0 APPROVED FOR VERTICAL OR HORIZONTAL MOUNTING MODEL FD 1050 thru FD 1500 FOR VERTICAL MOUNTING ONLY Cubic Feet CU FT Kilograms KG Cubic Meters CU M Inches IN Pounds LBS Millimeters MM V M E O R U O T N N I T L C I Y A N L G 14 Step 5 Locate bracket in desired position Vertical Sensor Valve Detector Head Up or Horizontal Figure 2 Using the bracket as a template mark and drill holes in bulkhead and...

Page 8: ...6 or 7 a Before attaching cable to the cylinder check that the cylinder bracket is located correctly and firmly mounted b With the cylinder strapped in its bracket pass the cable jacket ferrule completely through the hole in the cylinder manifold This will allow the necessary cable flexibility needed for inserting the offset end of the flexible shaft into the actuator lever After connecting the sh...

Page 9: ...l and making to determine the applicable DOT specification The discharged extinguisher may be refilled upon the prepaid return of the discharged system Contact factory or authorized dealer for detail RETURN TO UNITED STATES SEA FIRE MARINE Division of Metalcraft Inc 9331 A Philadelphia Road Baltimore Maryland 21237 USA EUROPE SEA FIRE EUROPE LTD Unit 7 io Centre Stephenson Road Fareham Hampshire P...

Page 10: ...icate the ability to discharge the agent but not the quantity of extinguishing agent The cylinder less bracket must be weighed on at least a semiannual basis and be replaced immediately if gross weight has decreased by quantity noted on the specification label Never paint or obstruct the cylinder manifold or sensor valve detector as this will adversely affect its operating characteristic FD models...