Note: the LED
flashes as soon as the START button is pressed and continues to flash until the frequency
stabilises if a "measurements" card has not been inserted and until the frequency and voltage stabilise if a "measurements"
card has been inserted.
Following stabilisation, the LED light comes on continuously.
3.1.2
Stopping the generating set
n
trigger the circuit breaker located at the base of the centre console
o
Let the motor run under no load for 1 to 2 minutes to allow it to cool.
p
press the "STOP" button to stop the generating set.
q
switch off the MICS Nexys module by switching the key to "OFF" (without forcing it).
3.2.
Automatic mode
3.2.1
Starting the generating set
Danger
When the command / control module is operational (key switch turned to ON), the generating set may
start without warning, upon issue of an external starting command (if the module is equipped with this
option).
When the external command is activated, the "AUT" pictogram appears.
Sequence
Screen display
n
5-second delay (if this programming has been
performed) to take micro breaks on the line into
account.
The third line on the screen displays the time
remaining for the line micro break.
At the end of this delay, two scenarios are possible:
Generating set with air preheating option
Sequence
Screen display
LED status
o
Air preheating for 10 seconds
p
Starting
Flashing:
q
Generating set runs at a stable speed
Continuously lit:
In this case, charging is possible.