15/22
Ref. GPAO : 33502017201_1_1
4.5.
List of alarms associated with a pictogram
Low fuel level alarm: Indicates the need to fill up with
fuel.
Associated pictogram
"Alternator charging fault" alarm indicates a problem
affecting the alternator charging rate.
Associated pictogram
5.
Special notes
y
Emergency stop
If the shunt on terminal block B11 is removed (control console interior), the generating set stops immediately due to an emergency
stop fault. This terminal block is used for connecting the external emergency stop device (cover or set site).
y
Protection fuse
If the fuse blows during operation, the generating set will stop without indicating a fault. It is then necessary to switch the key
switch to OFF, locate the cause of the fault, replace the fuse then switch the switch back to ON.
y
MANU and AUTO modes
If the set is started in manu mode (START button) and an external command is received, this takes priority over manu mode. The
generating set will only stop if the external command disappears. Pressing STOP, causes the generating set to stop immediately, a
general fault appears (LED) and the
SOS 010
fault code appears.
000
.
y
AUTO mode with programmed delays
When an external command is received, the "AUT" pictogram flashes during the line micro break and restoration phases as well as
during the starting and speed/frequency stabilisation phases.
y
AUTO mode with non-programmed delays
When an external command is received, the "AUT" pictogram flashes during the starting and speed/frequency stabilisation phases.
Once the external command is no longer being received, the "AUT" LED pictogram stops flashing.
y
Starting and stopping the generating set
¾
If the engine has not reached 1000 rpm when the set is started and 5 seconds after the starter power has been cut, the
generating set stops due to a non-starting fault.
¾
In the event of an alternator charging fault, the corresponding pictogram appears (this fault is interpreted as a warning).
¾
If the STOP button is pressed or the external order associated with the power return is no longer present, the generating
set stops normally. It will only be possible to restart the set after the engine has been stopped completely at a frequency <
7.5 Hz and a delay of 3 seconds has elapsed.