3.1.
Manual mode
3.1.1
Starting the generating set
Danger
Check that the generating set circuit breaker has triggered.
n
connect the generating set battery.
o
turn the key switch to the ON position (without forcing it)
9
All of the LEDs light up for 2 seconds, to confirm that they are operating correctly.
9
If the LEDs do not light up, check the protection fuse and replace it if necessary.
9
All the items on the screen are displayed for 2 seconds.
9
Only the "ON" LED remains lit to indicate that the module is powered up.
9
The following screen appears.
The first line displays the motor speed in RPM.
The second line displays the battery voltage in
volts (V).
9
Check the battery voltage (min. 12 V)
p
Press (once briefly) the green "START" button.
9
If the motor is equipped with an air preheating system, there is a 10-second delay before the motor starts
(preheating activation period).
9
The following screen appears
The third line displays the air preheating time
remaining (with pictograms representing a
resistor and an hourglass).
9
If the motor is not fitted with an air preheating system or once the preheating delay has elapsed, the engine starts
up (start of a cycle comprising 3 attempts to start up the engine).
9
The following screen appears.
Warning
The number of successive and automatic starting attempts is limited to 3.