Scotsman SLE400R User Manual Download Page 19

Service Diagnosis:

SYMPTOM

POSSIBLE CAUSE

PROBABLE FIX

No ice is made, nothing operates

Unit off, due to no power

Restore power

Unit off, due to ICE/OFF/WASH
switch in OFF position

Switch ICE/OFF/WASH switch to
ICE

Unit off, due to bin thermostat
closed

Check temperature at bin
thermostat bracket, if warmer than
40

o

F., thermostat should be

open. Adjust/replace thermostat.

Unit off, due to high pressure cut
out open

Check fan motor.

No ice, compressor off

No cooling due to compressor not
operating

Check compressor for voltage,
continuity, and operation. Check
starting components. Replace if
found to be faulty.

If no voltage, check contactor,
replace if coil or contacts open.

Check temperature of
compressor, if hot may be lack of
refrigerant, defective TXV or
compressor

Unit off, due to low pressure
(pump down) control open.

Check liquid line valve coil for
power and/or continuity

No ice is made, compressor is
operating

No water due to water turned off.

Reconnect water supply

No water due to water filter
plugged.

Replace water filter

No water due to strainer screen
plugged

Clean out inlet screen

No water due to inlet water valve
will not open

Replace valve

Water in reservoir, but no water
over evaporators

Water pump does not work,
replace pump

No cooling at evaporator due to
hot gas valve leaking thru

Replace hot gas valve

No cooling at evaporator due to
fan not turning

Check & replace fan motor.

Fan and pump do not have
power; hot gas valve opens and
closes.

Coil or relay open, replace relay.

No cooling at evaporator due to
dirty condenser

Clean condenser

No cooling due to compressor not
pumping

Check system pressures, replace
compressor if not pumping

SLE400R

January 1995

Page 19

Summary of Contents for SLE400R

Page 1: ...warning symbol where it appears in this manual It is an alert for important safety information on a hazard that might cause serious injury Keep this manual for future reference This manual was printe...

Page 2: ...s used to determine wire size and type per the National Electric Code Note Do not connect this refrigeration system to a used condenser circuit Only the condenser and line set specified for this machi...

Page 3: ...factured with the highest regard for safety and performance They meet or exceed the standards of UL NSF and CSA Scotsman assumes no liability or responsibility of any kind for products manufactured by...

Page 4: ...itions Have the water tested Acidic water or alkaline water will both cause corrosion Dissolved solids cannot be filtered out Softened water is not recommended Never use de ionized water Reverse osmos...

Page 5: ...ea 3 Locate and uncoil a portion of the bin thermostat capillary tube Route the end of the capillary tube into the plastic tube in the base of the ice machine next to the compressor and through the bi...

Page 6: ...nd of the capillary tube thru the tube watch the capillary as it comes out of the base line it up with the inlet hole of the thermostat bracket and push it into the hole Move the cabinet of the ice ma...

Page 7: ...kit place the stainless steel adapter onto the top of the dispenser Follow all directions included with the kit 8 After the ice machine has been placed on the dispenser remove the front panel and unc...

Page 8: ...igid and meet local code Traps in the bin drain line without vents ahead of them will cause poor draining The bin drain must be vented if there is a long horizontal run 5 or more The reservoir drain m...

Page 9: ...condenser and to the ice machine Be certain that there is no metal to metal or tight tube to tube contact between the liquid and discharge lines Coil excess tubing inside the building in a horizontal...

Page 10: ...ections to the wires in the junction box A ground screw is provided in the junction box Follow All Local Codes This Unit Must Be Grounded Usually a licensed electrician will be required to connect the...

Page 11: ...l 8 Is the ice machine connected to a 230 volt electrical power supply and is the ice machine the only load on that circuit 9 Has all of the shipping material been removed from the inside of the cabin...

Page 12: ...e control adjustment ICE OFF WASH switch Control box Ice Thickness Control ICE OFF WASH Switch Bin Thermostat Water Distributor Pan Bin Thermostat Bracket Water Inlet Valve Strainer Water Pump Control...

Page 13: ...he ICE OFF WASH switch to ON 11 The remote fan motor will begin to turn and warm air will be discharged from the top of the remote condenser 12 The water temperature in the reservoir will soon be 320...

Page 14: ...motor and the pump motor The Harvest Termination Thermostat is closed to NC but there is no power thru it The ice size thermostat heater is on and the compressor contactor coil is energized Harvest In...

Page 15: ...r 1 Mix the bleach and water using the ratio of two ounces of bleach to two gallons of water 2 Wipe all interior surfaces of the ice storage bin with the bleach and water 3 Allow to air dry To Remove...

Page 16: ...e 17 Remove the water distributor pan 18 Mix a sanitizer solution of 1 ounce of household bleach to 2 gallons of warm 95o F 115o F water 19 Wash the splash guard and the water distributor pan with the...

Page 17: ...mote condenser Water Water flows into the ice machine from its inlet connection at the back of the cabinet through the inlet water valve and into the reservoir The water in the reservoir is pumped up...

Page 18: ...Discharge Pressure In Harvest 130 150 PSIG Typical Compressor Amp Draw 4 5 during freeze cycle 5 6 during the harvest cycle Compressor Copeland RS64C1E CAV 214 Thermostatic Expansion Valve Superheat i...

Page 19: ...ive TXV or compressor Unit off due to low pressure pump down control open Check liquid line valve coil for power and or continuity No ice is made compressor is operating No water due to water turned o...

Page 20: ...ess than 550 F Warm up air or move machine Lack of heat during harvest due to water flowing thru water cooled condenser Replace water regulating valve Lack of heat during harvest due to lack of refrig...

Page 21: ...Replace valve if temps are nearly equal Compressor inefficient Check replace compressor Cubes are wrong size shape Ice size thermostat not adjusted properly Adjust ice size thermostat use gauge shipp...

Page 22: ...he ice size thermostat with the proper part number following the above steps from 9 1 Primary Resistor Heater 1 Disconnect electrical power 2 Disconnect the primary resistor s yellow wire from termina...

Page 23: ...rge hose from pump discharge port 8 Remove pump from ice machine 9 Reverse above steps to replace Inlet Water Valve The valve may plug up from minerals in the water and should then be cleaned rather t...

Page 24: ...iquid line dryer is required Polyol ester oil absorbs water very easily and when the system is opened for service it must be re sealed as soon as possible 15 minutes maximum Special leak detection equ...

Reviews: