Service Diagnosis: 

SYMPTOM

POSSIBLE CAUSE

PROBABLE FIX

No ice is made, nothing operates

Unit off, due to no power

Restore power

Unit off, due to ICE/OFF/WASH
switch in OFF position

Switch ICE/OFF/WASH switch  to
ICE

Unit off, due to bin thermostat
closed

Check temperature at bin
thermostat bracket, if warmer than
40

o

 F., thermostat should be

closed. Adjust/replace thermostat.

Unit off, due to relay K1 coil open. Check relay coil, if open replace

relay.

Water cooled unit off, due to high
pressure cut out open

Lack of water to condenser,
check water supply and water
regulating valve.

No ice, compressor off

No cooling due to compressor not
operating

Check compressor for voltage,
continuity, and operation. Check
starting components. Replace if
found to be faulty.

Check temperature of
compressor, if hot may be lack of
refrigerant, defective TXV or
compressor

No ice is made, compressor is
operating

No water due to water turned off.

Reconnect water supply

No water due to water filter
plugged.

Replace water filter

No water due to strainer screen
plugged

Clean out inlet screen

No water due to inlet water valve
will not open

Replace valve

Water in reservoir, but no water
over evaporators

Water pump does not work,
replace pump

No cooling at evaporator due to
hot gas valve leaking thru

Replace hot gas valve

No cooling at evaporator due to
fan not turning

Check & replace fan motor.

Fan and pump do not have
power; hot gas valve opens and
closes.

Coil or relay open, replace relay.

No cooling at evaporator due to
dirty condenser

Clean condenser

No cooling due to compressor not
pumping

Check system pressures, replace
compressor if not pumping

SLE300

January 1995

Page 19

Summary of Contents for SLE300

Page 1: ...ts Specifications page 2 Limitations page 3 Installation General page 4 Bin page 5 SLD dispenser page 6 RS or IS dispenser page 7 Plumbing page 8 Electrical page 9 Final Check List page 10 Component L...

Page 2: ...bins see sales literature for proper ice storage bin Minimum Circuit Ampacity is used to determine wire size and type per the National Electric Code 3 3 4 1 3 8 7 8 22 20 4 1 4 SLE300 Back View Air Co...

Page 3: ...and CSA Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman that have been altered in any way including the use of any part and or other components not s...

Page 4: ...ould be filtered Water filters vary greatly in ability and function Install one that filters out suspended solids to a dimension of 5 microns or less The finer the filter the better but finer filters...

Page 5: ...t of the cube drop area 3 Locate and uncoil a portion of the bin thermostat capillary tube Route the end of the capillary tube into the plastic tube in the base of the ice machine next to the compress...

Page 6: ...end of the capillary tube thru the tube watch the capillary as it comes out of the base line it up with the inlet hole of the thermostat bracket and push it into the hole Move the cabinet of the ice m...

Page 7: ...kit place the stainless steel adapter onto the top of the dispenser Follow all directions included with the kit 8 After the ice machine has been placed on the dispenser remove the front panel and unc...

Page 8: ...eet local code Traps in the bin drain line without vents ahead of them will cause poor draining The bin drain must be vented if there is a long horizontal run 5 or more The reservoir drain must be ven...

Page 9: ...rcuit breakers To make the electrical connections 1 Remove the right top panel 2 Remove the junction box cover 3 Make the electrical connections to the wires in the junction box A ground screw is prov...

Page 10: ...s 5 Have the drain connections been made 6 Have the drain connections been checked for leaks 7 Is the cabinet level 8 Is the ice machine connected to a 115 volt electrical power supply and is the ice...

Page 11: ...ce size control adjustment ICE OFF WASH switch Control box Ice Thickness Control ICE OFF WASH Switch Bin Thermostat Water Distributor Pan Bin Thermostat Bracket Water Inlet Valve Strainer Water Pump C...

Page 12: ...nd warm air will be discharged from the back of the ice machine On water cooled models warm water will begin to flow from the condenser drain 10 The water temperature in the reservoir will soon be 320...

Page 13: ...e fan and pump motors The Harvest Termination Thermostat is closed to NC but there is no power thru it The ice size thermostat heater is on and the compressor contactor coil is energized Harvest In th...

Page 14: ...rinse and an air dry is a basic procedure Every 30 days the liner should be sanitized with a commercial ice machine sanitizer according to the directions of the sanitizer or with a solution of househo...

Page 15: ...sanitizer solution of 1 ounce of household bleach to 2 gallons of warm 95o F 115o F water 19 Wash the splash guard and the water distributor pan with the solution of sanitizer Allow to air dry 20 Wit...

Page 16: ...ator and the water flowing over it From the evaporator the refrigerant flows back to the compressor through the suction line Water Schematic Water flows into the ice machine from its inlet connection...

Page 17: ...vaporator at its inlet The hot discharge gases warm up the evaporator enough to allow the surface of the ice frozen to the evaporator to melt The remaining ice will then fall off into the bin During t...

Page 18: ...time required to warm suction line to 55o F Typical Suction Pressure In Harvest Typical Discharge Pressure In Harvest High Pressure Cut Out Cuts out at 380 PSIG resets at 315 PSIG Thermostatic Expansi...

Page 19: ...ce if found to be faulty Check temperature of compressor if hot may be lack of refrigerant defective TXV or compressor No ice is made compressor is operating No water due to water turned off Reconnect...

Page 20: ...less than 550 F Warm up air or move machine Lack of heat during harvest due to water flowing thru water cooled condenser Replace water regulating valve Lack of heat during harvest due to lack of refri...

Page 21: ...e of tubes to and from hot gas valve there should be a temperature drop across the valve in the freeze cycle Replace valve if temps are nearly equal Compressor inefficient Check replace compressor Cub...

Page 22: ...control box 11 Replace the ice size thermostat with the proper part number following the above steps from 10 1 Primary Resistor Heater 1 Disconnect electrical power 2 Disconnect the primary resistors...

Page 23: ...pump cover from the machine 7 Pull discharge hose from pump discharge port 8 Remove pump from ice machine 9 Reverse above steps to replace Inlet Water Valve The valve may plug up from minerals in the...

Page 24: ...work Check with the leak detector manufacturer if in doubt LIQUID CHARGING Instructions for R 404A In preparation for charging the low side hose should have a sight glass and or a restrictor device su...

Reviews: