Installation: Product Specifications
Location Limitations:
The product is designed to be installed indoors, in
a controlled environment. Air cooled models
discharge very warm air into the room. Water
cooled models discharge warm water into the
building’s drain. Space needs to be provided for
service access.
Space Limitations
Do not block air flow at the front.
Airflow is in the front left and out the front right.
CU3030 also takes air in from below the cabinet.
Environmental Limitations
Minimum
Maximum
Air
temperature
50
o
F.
100
o
F.
Water
temperature
40
o
F.
100
o
F.
Water
pressure
20 psi
80 psi
Power supply – acceptable voltage ranges
Minimum
Maximum
115 volt model
104 volts
126 volts
230 volt model
198 volts
253 volts
Warranty Information
The warranty statement for this product is provided
separately from this manual. Refer to it for
applicable coverage. In general warranty covers
defects in material or workmanship. It does not
cover maintenance, corrections to installations, or
situations when the machine is operated in
circumstances that exceed the limitations printed
above.
Product Information
The product is a self contained cuber with bin. That
type of machine is designed to be free standing
can be built in under the counter.
May 2008
Page 2
CU1526, CU2026, CU3030
Service Manual
Air Flow