Remote Condenser Location
Use the following for planning the placement of the
condenser relative to the ice machine
Location Limits - condenser location must not
exceed ANY of the following limits:
•
Maximum rise from the ice machine to the
condenser is 35 physical feet
•
Maximum drop from the ice machine to the
condenser is 15 physical feet
•
Physical line set maximum length is 100 feet.
•
Calculated line set length maximum is 150.
Calculation Formula:
•
Drop = dd x 6.6 (dd = distance in feet)
•
Rise = rd x 1.7 (rd = distance in feet)
•
Horizontal Run = hd x 1 (hd = distance in
feet)
•
Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these
requirements must receive prior written
authorization from Scotsman.
Do NOT:
•
Route a line set that rises, then falls, then
rises.
•
Route a line set that falls, then rises, then
falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice
machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and
then 100 feet away horizontally. 35 x 1.7 = 59.5.
59.5 +100 = 159.5. 159.5 is greater than the 150
maximum and is NOT acceptable.
October 2010
Page 8
C2648
Remote Condenser Models - User Manual
22.87"
17.15"
40.35"
dd
hd
rd
Remote Condenser Located
ABOVE Ice Machine
Remote Condenser Located
BELOW Ice Machine
Condenser Distance &
Location Schematic
Max 35'
Max 15'