3.2 Fitting the mains and interface cables
a) Remove the required knock-outs from the base or side of the cabinet and fit the cable
glands provided.
b) Route the fire-rated mains cable through one of the cable glands and secure the Live,
Neutral and Earth wires into the screw terminal block provided. There should be minimal
slack cable inside the cabinet and care should be taken to ensure that there is at least 10
mm of clearance between the mains and any other cables. Do not coil up slack mains
cable inside the cabinet. Tighten the cable gland cover to clamp the cable.
Note: the mains input block contains a fuseholder fitted with a 0.5A AS 20 mm fuse.
Only replace with an identical rated fuse (a spare is supplied).
c) Uncoil the monitored FPLINK cable from inside the cabinet and route through the
second cable gland.
Do NOT cut the free end to shorten the cable, as this contains a resistor between the
screen (drain wire) and one of the cores (violet) for monitoring purposes
.