42
SEL-300G Relay
Quick-Start Guide
Date Code 20170804
SEL-300G Quick-Start Guide
Differential Element Commissioning Worksheet
Check List
Step 1. Phasor rotation is as expected.
Step 2. Circle your transformer and CT connection:
If E87 = G, OR
If E87 = T AND
TRCON = GEN, CTCON = Y
TRCON = DABY, CTCON = DAB
TRCON = YDAB, CTCON = Y
TRCON = DACY, CTCON = DAC
TRCON = YDAC, CTCON = Y
TRCON = DABDAB, CTCON = Y
TRCON = DACDAC, CTCON = Y
TRCON = YY, CTCON = Y
Then, phase angles should be 180° apart.
Plot Phasors
If E87 = T AND
TRCON = GEN, CTCON = DAC
TRCON = DABY, CTCON = Y
TRCON = YDAC, CTCON = Y
Then, I87 should lead IW1 by 150°.
If E87 = T AND
TRCON = GEN, CTCON = DAB
TRCON = DACY, CTCON = Y
TRCON = YDAB, CTCON = Y
Then, I87 should lag IW1 by 150°.
135
–90
–45
0
45
90
–135
180/–180