9.6
SEL-749M Relay
Instruction Manual
Date Code 20080918
Analyzing Events
Event Reporting
Figure 9.2
Sample Event History
Viewing the Event History
Access the history report from the communications ports, using the
HIS
command or the analysis menu within
AC
SEL
ERATOR
QuickSet
®
SEL-5030
software. View and download history reports from Access Level 1 and higher.
Use the
HIS
command from a terminal to obtain the event history. You can
specify the number of the most recent events that the relay returns. See
HISTORY Command on page U.7.16
for information on the
HIS
command.
Use the front-panel
MAIN > Events > Display Events
menu to display event
history data on the SEL-749M front-panel display.
Use the
AC
SEL
ERATOR
QuickSet software to retrieve the relay event history.
View the
Relay Event History
dialog box via the
Analysis > Get Event
Files…
menu.
Clearing
Use the
HIS C
command to clear or reset history data from Access Levels 1
and higher. Clear/reset history data at any communications port. This will
clear all event summaries, history records, and reports.
Event Reports
The latest event reports are stored in nonvolatile memory. Each event report
includes four sections:
➤
Analog values of current, voltage, and digital states of the
various Relay Word bits
➤
Digital states of the protection and control elements, including
overcurrent, and voltage elements, plus status of digital output
and input states
➤
Event Summary
➤
Settings in service at the time of event trigger, consisting of
Group, Logic, Global, and Report settings classes
Use the
EVE
command to retrieve the reports. There are several options to
customize the report format.
=>>
HIS <Enter>
SEL-749M Date: 12/10/2003 Time: 22:24:11.418
MOTOR RELAY Time Source: internal
# DATE TIME EVENT CURR TARGETS
1 12/03/2003 22:24:00.101 Overcurrent Trip 1049.2 11010000
2 12/03/2003 22:15:20.714 Overload Trip 1493.0 11100000
3 12/03/2003 15:21:10.663 Trigger 4.7 11000000
4 12/03/2003 15:21:07.512 PTC Trip 7.8 11000000
5 12/03/2003 10:49:34.103 Trigger 6.4 11000000
6 12/03/2003 10:49:30.040 PTC Trip 7.7 11000000
7 12/02/2003 20:50:54.846 Lockd Rotor Trip 1.2 11100000
8 12/02/2003 20:44:58.448 Lockd Rotor Trip 1494.4 11100010
9 12/02/2003 16:38:04.829 Trigger 1.4 10000000
Maximum
Current
Event
Type
User-Defined Target LEDs
[See
]
Event
Number
!
CAUTION
Changing the LER setting will clear all
events in memory. Be sure to save
critical event data prior to changing
the LER setting.
Summary of Contents for SEL-749M
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 14: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 20: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 52: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 118: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 224: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 286: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 306: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 310: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 314: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...