7.16
SEL-587Z Instruction Manual
Date Code 20020903
ASCII Command Reference
Command Definitions
Parameter
y
is the name of the first setting to display. If
y
is not specified, all
settings are shown in the selected settings class.
Sample
SHOWSET
commands showing all the factory settings are shown in
.
=>
SHO <Enter>
Relay Settings:
RID =BUS 1
TID =STATION A
CTR = 120 TDURD = 9.000
87A1P = 125 87A2P = 40 87B1P = 125 87B2P = 40
87C1P = 125 87C2P = 40
50P1P = OFF 50P2P = OFF 50P3P = OFF
50A1P = 2.5 50A2P = 1.0 50B1P = 2.5 50B2P = 1.0
50C1P = 2.5 50C2P = 1.0
51PP = OFF 51PC = U3 51PTD = 15.00 51PRS = N
51AP = OFF 51AC = U3 51ATD = 15.00 51ARS = N
51BP = OFF 51BC = U3 51BTD = 15.00 51BRS = N
51CP = OFF 51CC = U3 51CTD = 15.00 51CRS = N
50G1P = OFF 50G2P = OFF
51GP = OFF 51GC = U3 51GTD = 15.00 51GRS = N
50Q1P = OFF 50Q2P = OFF
51QP = OFF 51QC = U3 51QTD = 15.00 51QRS = N
CFD = 60.000
Press RETURN to continue
DMTC = 5 PDEMP = 5.00 GDEMP = 1.50 QDEMP = 1.50
SV5PU = 120.000 SV5DO = 0.000 SV6PU = 15.000 SV6DO = 0.000
SV7PU = 0.000 SV7DO = 0.000 SV8PU = 0.000 SV8DO = 0.000
SV9PU = 0.000 SV9DO = 0.000 SV10PU= 0.000 SV10DO= 0.000
SV11PU= 0.000 SV11DO= 0.000 SV12PU= 0.000 SV12DO= 0.000
SV13PU= 0.000 SV13DO= 0.000 SV14PU= 0.000 SV14DO= 0.000
NFREQ = 60 PHROT = ABC DATE_F= MDY
Figure 7.1
SHO Command Sample Display.
Table 7.5
Valid SHO Commands
Command
Settings Class
SHO
Relay settings
SHO L
SEL
OGIC®
control equation settings
SHO P 1
Rear port settings
SHO P F
Front port settings
SHO R
Sequential Events Recorder (SER) settings
SHO T
Text label settings
Summary of Contents for SEL-587Z
Page 10: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 66: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 162: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...